2011-05-05 08:07:30 | DRAMA WORKS | | PERMIT NUMBER 11030136 | | | | | | 1. THE FINAL OCCUPANT LOAD FOR THE FACILITY IS EXPECTED | | TO BE DISCUSSED AT A FUTURE MEETING. SEVERAL NUMBERS | | HAVE BEEN IDENTIFIED EITHER ON THE PLANS OR IN | | CORRESPONDENCE. | | | | 2. PROVIDE STANDPIPE HOSE VALVES FOR STAGES GREATER | | THAN 1,000 SQUARE FEET. | | | | 3. PROVIDE 18" DEEP DRAFT STOPS AND CLOSELY SPACED | | SPRINKLERS AROUND LOBBY FLOOR OPENING TO SECOND FLOOR. | | | | 4. CONSTUME AND STORAGE AREAS SHALL BE DESIGNED AS | | ORDINARY HAZARD AND NOT LIGHT HAZARD. | | | | 5. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM | | SYSTEM. |
|