2011-05-05 08:07:30DRAMA WORKS
 PERMIT NUMBER 11030136
  
  
 1. THE FINAL OCCUPANT LOAD FOR THE FACILITY IS EXPECTED
 TO BE DISCUSSED AT A FUTURE MEETING. SEVERAL NUMBERS
 HAVE BEEN IDENTIFIED EITHER ON THE PLANS OR IN
 CORRESPONDENCE.
  
 2. PROVIDE STANDPIPE HOSE VALVES FOR STAGES GREATER
 THAN 1,000 SQUARE FEET.
  
 3. PROVIDE 18" DEEP DRAFT STOPS AND CLOSELY SPACED
 SPRINKLERS AROUND LOBBY FLOOR OPENING TO SECOND FLOOR.
  
 4. CONSTUME AND STORAGE AREAS SHALL BE DESIGNED AS
 ORDINARY HAZARD AND NOT LIGHT HAZARD.
  
 5. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 SYSTEM.