2011-03-28 13:22:36 | PALM BEACH DRAMAWORKS |
| PERMIT NUMBER 11030136 |
| |
| 1) PLEASE PROVIDE SEPARATE PLANS AND PERMIT FOR THE |
| RELOCATION OF THE GAS METER AND APPURTENANT PIPING TO |
| THE CONSTRUCTION SERVICES DEPARTMENT. |
| |
| 2) NO DAMAGE IS TO OCCUR TO THE EXISTING FIRE SPRINKLER |
| SYSTEM. |
| |
| 3) THE "ACCESS DOOR TO REMAIN" FOR THE ROOF LOCATED |
| NEAR THE STAIRS IS TO BE MARKED NO EXIT. |
| |
| 4) ADDITIONAL EXIT SIGNS APPEAR TO BE NEEDED ON THE |
| FIRST LEVEL. IN SOME CASES BLIND CORNERS EXIST ABSENT |
| OF EXIT SIGNS. (LS100) ALSO EXIT SIGNS APPEAR TO BE |
| MISSING ALONG THE NARCISSUS AVENUE SIDE. |
| |
| 5) EXIT SIGN MISSING FROM EXIT DOOR LEADING TO ALLY, |
| NORTH SIDE. (LS100) |
| |
| 6) ADDITIONAL EXIT SIGNS APPEAR TO BE NEEDED ON THE |
| SECOND LEVEL. PLEASE REVIEW. |
| |
| 7) ELEVATOR WARNING SIGNS NEEDED AT EACH ELEVATOR |
| OPENING. |
| |
| 8) ASTERICS SHOWN ON THE SECOND FLOOR ACCESSIBILITY |
| PLAN DEPICTS WHAT. |
| |
| 9) PLEASE FURTHER EXPLAIN TRIPPING HAZARD NOTE ON SHEET |
| A100. WHAT IS THE ELEVATION DIFFERENCE. |
| |
| 10) THE EXISTING FIRE DEPARTMENT CONNECTION SHALL BE |
| INSPECTED TO ENSURE PROPER OPERATION. BOTH CONNECTIONS |
| SHALL FREELY SWIVEL AND CAPS ARE TO BE MAINTAINED. |
| |
| 11) SOFFITS SHALL NOT INTERFERE WITH THE OPERATION OF |
| ANY AUTOMATIC FIRE SPRINKLER HEADS. |
| |
| 12) HOW WILL EXIT ACCESS BE MAINTAINED IN COSTUME SHOP |
| 209 DISPLAYED ON THE SECOND FLOOR. |
| |
| 13) PLEASE PROVIDE MORE DETAILS ON INTERSTITIAL SPACE |
| ABOVE NEW ADMINISTRATIVE OFFICE. WHAT IS PRESENT, IS |
| THERE ACCESS, AND IS THIS AREA PROTECTED BY AUTOMATIC |
| FIRE SPRINKLERS. (TECHNICAL LEVEL CATWALK PLAN) |
| |
| 14) PLEASE INDICATE PRESCRIPTIVE STRENGTH REQUIREMENTS |
| FOR NEW CATWALKS, HANGERS, AND HANDRAILS SHOWN ON THE |
| TECHNICAL LEVEL/CATWALK PLAN. PLEASE INDICATE HEIGHTS |
| OF NEW HANDRAILS. |
| |
| 15) SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE |
| SPRINKLER SYSTEM REMODELING. |
| |
| 16) SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE |
| SPRINKLER SYSTEM REMODELING. |
| |
| 17) EXISTING EXIT SIGNS AND EMERGENCY LIGHTS ARE TO BE |
| INSPECTED TO ENSURE PROPER OPERATION. |
| |
| 18) ADDITIONAL SIGNALING FIRE ALARM DEVICES APPEAR TO |
| BE NEEDED. NO FIRE ALARM DEVICES ARE PRESENT IN |
| REHEARSAL SPACE 201. SOME BATHROOMS ARE ABSENT OF |
| SIGNALING APPLIANCES. |
| |
| 19) ALL HANDRAILS AND GUARDRAILS TO MEET THE |
| PRESCRIPTIVE STRENGTH REQUIREMENTS. |
| |
| 20. PLEASE PROVIDE FLAME-SPREAD DETAILS FOR TECTUM |
| FINALE ACOUSTIC WALL PANEL. |
| |
| 21. SECURITY DEVICES INSTALLED ON DOORS SHALL NOT |
| INTERFERE WITH ANY EXITING. |
| |
| 22. ALL NEW FIRE WALLS ARE TO BE PROPERLY IDENTIFIED. |
| |
| 23. NO COMBUSTIBLES ALLOWED IN THE RETURN AIR PLENUM AS |
| DESCRIBED ON THE PLANS. |
| |
| 24. ALL NEW FIRE DAMPERS ARE TO BE DROP TESTED TO |
| ENSURE PROPER FUNCTION. |
| |
| |
| |
| MIKE CARSILLO, BATTALION CHIEF |
| BUREAU OF FIRE PREVENTION |