Review Stop FIRE
Sequence Number 2
Notes
Date Text
2012-01-18 13:14:092100 NORTH FLORIDA MANGO ROAD
 PERMIT #11030040
 MASTER #10080396
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER NFPA 24, BUILDINGS LESS THAN 40 FT IN HEIGHT, A
 BACKFLOW PREVENTER SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FT BUT AT LEAST AS FAR FROM THE BUILDING
 AS THE HEIGHT OF THE WALL FACING THE BACKFLOW
 PREVENTER.
  
 PROVIDE LOCKABLE CAPS ON FIRE DEPARTMENT CONNECTION.
 PROVIDE WEATHERPROOF SIGNAGE FOR FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE CHAIN AND LOCK ON BACKFLOW PREVENTER.
  
 THE HYDRAULIC CALCULATIONS SUBMITTED WERE NOT SIGNED
 AND SEALED BY THE ENGINEER.
  
 DESIGN AREA #1 HAS LIGHT HAZARD SPACING UP TO 14.5'X14'
 (203 SQ.FT.); HOWEVER, THE HYDRAULIC CALCULATIONS DO
 NOT INDICATE ANY SPRINKLERS HAVING A FLOW OF 20.3
 GALLONS PER MINUTE.
  
 THE REDUCED AREA HYDRAULIC CALCULATIONS SUPPORT THREE
 SPRINKLERS SUPPLIED FROM A 1-1/4" BRANCHLINE; HOWEVER,
 SEVERAL BRANCH LINES HAVE ANYWHERE FROM 4-10 SPRINKLERS
 LOCATED WITHIN A SPAN OF 37' FEET ON THE BRANCH LINE
 WHICH WOULD RESULT IN A GREATER HYDRAULIC DEMAND ON THE
 SYSTEM. PROVIDE HYDRAULIC CALCULATIONS SUPPORTING THE
 ADDITIONAL SPRINKLERS.
  
 PROVIDE HYDRAULIC CALCULATIONS FOR THE ORDINARY HAZARD
 AREA (STORAGE #18 AND #19).
  
 FOUR SOFFITS 8'-0" AFF DO NOT APPEAR TO HAVE COVERAGE.
 SEE HALL #37 AND LOBBY #11 WITH ADJACENT RESTROOMS.
  
 SUBMIT PRODUCT DATA FOR SIDEWALL SPRINKLERS. ADD
 SIDEWALL SPRINKLER COUNT TO SPRINKLER SCHEDULE.
  
 THE SPRINKLER RISER DOES NOT APPEAR TO BE ACCESSIBLE.
 THE SPRINKLER RISER DETAIL DOES NOT INDICATE AN ALARM
 CHECK VALVE OR WATERFLOW SWITCH, INSPECTOR'S TEST
 CONNECTION, MAIN DRAIN, PRESSURE GAUGE ETC.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW