2011-03-15 10:15:392100 NORTH FLORIDA MANGO ROAD
 PERMIT #11030040
 MASTER #10080396
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 PROVIDE SPRINKLER PROTECTION FOR EMERGENCY GENERATOR
 ROOM ATTACHED TO SOUTHWEST AREA OF BUILDING.
  
 TYCO EC-8 EXTENDED COVERAGE SPRINKLERS ARE NOT UL
 LISTED FOR ORDINARY HAZARD APPLICATIONS SUCH AS STORAGE
 ROOMS AND LOADING ZONE. REVISE HYDRAULIC CALCULATIONS.
  
 THE HYDRAULIC CALCULATION FOR THE EXTERIOR OVERHANG
 SHOULD INCLUDE ALL SPRINKLERS PROTECTING THIS SPACE.
 EXTENDED COVERAGE SPRINKLER NOT LISTED FOR ORDINARY
 HAZARD APPLICATIONS. REVISE CALCULATIONS.
  
 THE HYDRAULIC AREA FOR THE KITCHEN WAS CALCULATED
 PERPENDICULAR TO THE BRANCH LINES. NFPA 13 REQUIRES THE
 HYDRAULIC AREA TO BE MEASURED PARALLEL TO BRANCH LINES.
 REVISE CALCULATIONS.
  
 PROVIDE SPRINKLER COVERAGE BELOW OVERHEAD GARAGE DOORS
 IN STORAGE ROOM 19.
  
 PROVIDE LOCKABLE CAPS ON FIRE DEPARTMENT CONNECTION.
 PROVIDE WEATHERPROOF SIGNAGE FOR FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE CHAIN AND LOCK ON BACKFLOW PREVENTER.
  
 SPRINKLER DESIGN SHALL CONFORM TO THE 2002 EDITION OF
 NFPA 13.
  
 JOB VALUE ON PERMIT APPEARS TO BE UNDERVALUED AT 1.41
 DOLLARS PER SQUARE FOOT. JOB VALUE SHALL INCLUDE TOTAL
 CONTRACT AMOUNT INCLUDING MATERIALS, LABOR AND
 OVERHEAD/PROFIT. PROVIDE A SIGNED COPY OF THE OFFICIAL
 CONTRACT.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW