| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| |
| PROVIDE SPRINKLER PROTECTION FOR EMERGENCY GENERATOR |
| ROOM ATTACHED TO SOUTHWEST AREA OF BUILDING. |
| |
| TYCO EC-8 EXTENDED COVERAGE SPRINKLERS ARE NOT UL |
| LISTED FOR ORDINARY HAZARD APPLICATIONS SUCH AS STORAGE |
| ROOMS AND LOADING ZONE. REVISE HYDRAULIC CALCULATIONS. |
| |
| THE HYDRAULIC CALCULATION FOR THE EXTERIOR OVERHANG |
| SHOULD INCLUDE ALL SPRINKLERS PROTECTING THIS SPACE. |
| EXTENDED COVERAGE SPRINKLER NOT LISTED FOR ORDINARY |
| HAZARD APPLICATIONS. REVISE CALCULATIONS. |
| |
| THE HYDRAULIC AREA FOR THE KITCHEN WAS CALCULATED |
| PERPENDICULAR TO THE BRANCH LINES. NFPA 13 REQUIRES THE |
| HYDRAULIC AREA TO BE MEASURED PARALLEL TO BRANCH LINES. |
| REVISE CALCULATIONS. |
| |
| PROVIDE SPRINKLER COVERAGE BELOW OVERHEAD GARAGE DOORS |
| IN STORAGE ROOM 19. |
| |
| PROVIDE LOCKABLE CAPS ON FIRE DEPARTMENT CONNECTION. |
| PROVIDE WEATHERPROOF SIGNAGE FOR FIRE DEPARTMENT |
| CONNECTION. |
| |
| PROVIDE CHAIN AND LOCK ON BACKFLOW PREVENTER. |
| |
| SPRINKLER DESIGN SHALL CONFORM TO THE 2002 EDITION OF |
| NFPA 13. |
| |
| JOB VALUE ON PERMIT APPEARS TO BE UNDERVALUED AT 1.41 |
| DOLLARS PER SQUARE FOOT. JOB VALUE SHALL INCLUDE TOTAL |
| CONTRACT AMOUNT INCLUDING MATERIALS, LABOR AND |
| OVERHEAD/PROFIT. PROVIDE A SIGNED COPY OF THE OFFICIAL |
| CONTRACT. |
| |