2011-03-15 09:48:432007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C PER
 FBC R301.2.1.4.3. PLEASE CORRECT.
  
 2) THE COMPONENT AND CLADDING PRESSURES FOR THE WINDOW
 AND DOOR ON SHEET A01 NEED TO BE INCREASED TO REFLECT
 EXPOSURE C.
  
 3) SHOW COMPLIANCE WITH FBC R703.6.3 WHICH REQUIRES A
 BOND BREAK BETWEEN THE EXTERIOR STUCCO AND THE REQUIRED
 WATER RESISTIVE BARRIER.
  
 4) SHOW COMPLIANCE WITH ASTM 1063 REQUIRES A WEEP
 SCREED AT THE BOTTOM OF ALL FRAMED EXTERIOR WALLS BELOW
 THE FLOOR LINE. FBC 703.6
  
 5) SHOW COMPLIANCE WITH FBC R704.1 FOR THE 6 INCH
 CLEARANCE BETWEEN EXTERIOR WALL COVERINGS AND FINAL
 EARTH GRADE FOR INSPECTION FOR TERMITES.
  
 6) PLANS WILL BE REQUIRED TO BE REVIEWED BY PALM BEACH
 COUNTY TO DETERMINE IF IMPACT FEES ARE DUE. THE PLANS
 THAT HAVE BEEN STAMPED BY THE COUNTY AND A COPY OF THE
 PAID RECEIPT ARE REQUIRED TO BE SUBMITTED BEFORE THE
 PERMIT IS ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714