Plan Review Notes
Plan Review Notes For Permit 11020623
Permit Number 11020623
Review Stop E
Sequence Number 1
Notes
Date Text
2011-03-14 15:20:31REQUEST FOR ADDITIONAL INFORMATION: SHEET E-9
  
 THE NEW 480 VOLT SERVICE REQUIRES A NEUTRAL CONDUCTOR
 FROM THE UTILITY. NEC 250.24 (C)
 THE NEW 480 VOLT SERVICE NEEDS TO BE GROUNDED. NEC
 250.20
 PROVIDE SPECIFICATION ON THE SERVICE INDICATING THE
 EQUIPMENT IS SUFFICIENT TO INTERRUPT THE AVAILABLE
 FAULT CURRENT. NEC 110.9
 PROVIDE A FAULT CURRENT CALCULATION TO SUPPORT THE
 EQUIPMENT SELECTION. NEC 110.10
 THE EQUIPMENT WITH SERVICE DISCONNECT MUST BE LISTED AS
 BEING SUITABLE AS SERVICE EQUIPMENT. NEC 225.36, 230.70
 PROVIDE A DETAIL FOR GROUNDING AND BONDING WITHIN THE
 HANDHOLDS. NEC 250.4
 PROVIDE SPECIFICATION ON THE PUMP CONTROL PANEL
 INDICATING THIS EQUIPMENT HAS BEEN LISTED BY A
 NATIONALLY RECOGNIZED TESTING AGENCY FOR THE INTENDED
 USE. NEC 110.3
  
 ROBERT LECKY, ELECTRICAL PLANS REVIEW, 561-805-6718
  
  
  