2011-02-22 15:24:43 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW CHECKLIST. |
| 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| |
| 1- BUILDING VALUE IS MORE THAN $300,000. NEED TO |
| PROVIDE ROOF TO WALL ENGINEERING EVALUATION TO SHOW |
| COMPLIANCE WITH THE MITIGATION SEC. 611.8 OF 2009 |
| REVISIONS TO THE 2007 FLORIDA BUILDING CODE- EXISTING |
| BUILDING. |
| |
| 2- FLAT ROOF: PROVIDE SIGNED AND SEALED RAS 117 |
| CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7 ON |
| LAST PAGE OF NOA 08-0410.09 SUBMITTED. |
| |
| ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117 |
| CALCULATIONS TO TAKE INTO CONSIDERATION THAT THIS |
| BUILDING IS LOCATED ON EXPOSURE "C". |
| |
| 3- CLEARLY IDENTIFY ON POLYFOAM POLYPRO AH160 PRODUCT |
| APPROVAL SUBMITTED WHAT'S THE TILE PROFILE TO VERIFY |
| COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF |
| 2007 FLORIDA RESIDENTIAL CODE. SEE TABLE 1 OF FLORIDA |
| PRODUCT APPROVAL FL6332-R2 SUBMITTED. |
| |
| 4- ROOF TILE FLORIDA PRODUCT APPROVAL. PROVIDE |
| CURRENT/REVISED FLORIDA PRODUCT APPROVAL FL7473- R2. GO |
| TO THE FLORIDA PRODUCT APPROVAL WEBSITE AND DOWNLOAD |
| CURRENT FLORIDA PRODUCT APPROVAL. AND, IDENTIFY WHICH |
| TYPE OF TILE IS GOING TO BE INSTALLED. |
| |
| 5- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| FLORIDA STATUTE. |
| |