Plan Review Notes For Permit 11020301 |
Permit Number |
11020301 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2011-04-08 07:35:14 | 2009 FBC W/2009 REVISIONS | | | | DENIED BY BUILDING | | | | 1) THE WINDOW AND DOOR PRESSURES SPECIFIED ON SHEET A-1 | | OF THE PLANS ARE STILL INCORRECT. THE PRESSURES FOR 140 | | MPH EXPOSURE C SHOULD BE +42.7 PSF, -57.2 PSF FOR THE | | WINDOWS (10 SQFT EFFECTIVE WIND AREA) LOCATED IN WALL | | ZONE 5. THE DOOR IN WALL ZONE 4 SHOULD BE +41.6 PSF, - | | 45.2 PSF (15 SQFT EFFECTIVE WIND AREA). THE WINDOWS | | LOCATED IN WALL ZONE 4 (10 SQFT EFFECTIVE WIND AREA) | | SHOULD HAVE PRESSURES OF +42.7 PSF, -46.3 PSF. SEE FBC | | TABLES R301.2(2) AND TABLE R301.2(3) AND ASCE 7-05 | | FIGURE 6-3. IF YOU DO NOT AGREE PLEASE SUBMIT SIGNED | | AND SEALED CALCULATIONS FROM THE ENGINEER SHOWING HOW | | THE PRESSURE WERE DETERMINED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|