Date Text
2011-04-08 07:35:142009 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE WINDOW AND DOOR PRESSURES SPECIFIED ON SHEET A-1
 OF THE PLANS ARE STILL INCORRECT. THE PRESSURES FOR 140
 MPH EXPOSURE C SHOULD BE +42.7 PSF, -57.2 PSF FOR THE
 WINDOWS (10 SQFT EFFECTIVE WIND AREA) LOCATED IN WALL
 ZONE 5. THE DOOR IN WALL ZONE 4 SHOULD BE +41.6 PSF, -
 45.2 PSF (15 SQFT EFFECTIVE WIND AREA). THE WINDOWS
 LOCATED IN WALL ZONE 4 (10 SQFT EFFECTIVE WIND AREA)
 SHOULD HAVE PRESSURES OF +42.7 PSF, -46.3 PSF. SEE FBC
 TABLES R301.2(2) AND TABLE R301.2(3) AND ASCE 7-05
 FIGURE 6-3. IF YOU DO NOT AGREE PLEASE SUBMIT SIGNED
 AND SEALED CALCULATIONS FROM THE ENGINEER SHOWING HOW
 THE PRESSURE WERE DETERMINED.
  