2011-02-28 09:57:46 | 2007 FBC W/2009 |
| |
| DENIED BY BUILDING |
| |
| 1) SUBMIT A COPY OF THE PAID RECEIPT FOR THE COUNTY |
| IMPACT FEES. |
| |
| 2) THE FLORIDA PRODUCT APPROVAL COVERSHEETS FOR THE |
| WINDOWS, MULLIONS AND DOORS ARE FOR THE 2004 CODE |
| VERSION. SUBMIT THE ONES FOR THE 2007 CODE VERSION. |
| |
| 3) THE FLORIDA PRODUCT APPROVAL COVERSHEET FOR THE DOOR |
| IS FROM A DIFFERENT MANUFACTURER (BENCHMARK) THAN THE |
| ATTACHED MIAMI-DADE NOA (JELD-WEN). THE FILE STATUS IS |
| CLOSED FOR THE NOA NO. 07-0731.04. SUBMIT CURRENT |
| PRODUCT APPROVAL THAT HAS BEEN REVIEWED AND APPROVED BY |
| THE DESIGNER OF RECORD. |
| |
| 4) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE FIXED |
| GLASS WINDOW IN THE NEW BEDROOM. |
| |
| 5) THE ENERGY CALCULATION FORM THAT WAS SUBMITTED |
| REQUIRES CEILINGS TO BE INSULATED TO A MINIMUM OF R-30. |
| THE PLANS SPECIFY R-19 INSULATION IN THE CEILINGS AND |
| THE FORM HAS R-19. IN ORDER TO USE THIS METHOD EACH |
| COMPONENT IS REQUIRED TO MEET OR EXCEED THE PERFORMANCE |
| CRITERIA ON THE FORM, OTHERWISE METHOD A MUST BE USED. |
| PLEASE CORRECT. |
| |
| 6) THE OWNER/AGENT IS REQUIRE TO SIGN THE ENERGY |
| CALCULATION FORMS. |
| |
| 7) SHOW COMPLIANCE WITH FBC R703.6.3 FOR THE REQUIRED |
| BOND BREAK BETWEEN THE WATER-RESISTIVE BARRIER AND THE |
| EXTERIOR STUCCO. |
| |
| 8) SHOW COMPLIANCE WITH FBC R703.6.2 AND ASTM C 1063 |
| FOR THE FOUNDATION WEEP SCREED AT THE BOTTOM OF ALL |
| FRAMED EXTERIOR WALLS BELOW THE FLOOR LINE WHERE THE |
| WALL IS SUPPORTED BY A FLOOR OR FOUNDATION. |
| |