Plan Review Notes For Permit 11020297 |
Permit Number |
11020297 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2011-03-14 08:36:57 | ****PROVISO**** | | ****REVISION REQUIRED**** | | ****ISSUED AT CONTRACTOR'S RISK**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | REVISE INSTALLATION SCHEDULE AS FOLLOWS: | | | | 1. (COMMENT FROM REVIEW #2) - THE ANCHOR SPACING DOES | | NOT COMPLY WITH REQUIREMENTS OF THE PRODUCT APPROVAL. | | FOR INSTANCE, SEE OPENING 1. C2 CONNECTION TYPE, BLOCK | | SUBSTRATE, -70PSF REQUIRES 4" SPACING, SEE CHART ON | | SHEET 10. THIS COMMENT APPLIES TO OTHER OPENINGS. | | PLEASE CHECK ALL AND REVISE INSTALLATION SCHEDULE AS | | REQUIRED. | | | | REVIEW #3 - COMMENT FROM REVIEW #2 PARTIALLY ADDRESSED | | - SOME OPENINGS (SUCH AS OPENING 1) SPECIFY DIFFERENT | | ANCHOR SPACING FOR TOP AND BOTTOM ALTHOUGH BOTH | | CONNECTIONS HAVE THE SAME CONNECTION TYPE, WIND DESIGN | | PRESSURE, AND SPAN. SEE OPENING 1, 12" SPACING DOES NOT | | MEET THE REQUIREMENT OF THE PRODUCT APPROVAL FOR 34" | | SPAN, 2.5" EDGE DISTANCE, BLOCK SUBSTRATE. | | | | PLEASE REVISE. PLEASE HAVE THE QUALIFIER VERIFY | | ACCURACY OF INSTALLATION SCHEDULE PRIOR TO SUBMITTAL. | | | | | | | | | | |
|