Plan Review Notes
Plan Review Notes For Permit 11020297
Permit Number 11020297
Review Stop B
Sequence Number 3
Notes
Date Text
2011-03-14 08:36:57****PROVISO****
 ****REVISION REQUIRED****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 REVISE INSTALLATION SCHEDULE AS FOLLOWS:
  
 1. (COMMENT FROM REVIEW #2) - THE ANCHOR SPACING DOES
 NOT COMPLY WITH REQUIREMENTS OF THE PRODUCT APPROVAL.
 FOR INSTANCE, SEE OPENING 1. C2 CONNECTION TYPE, BLOCK
 SUBSTRATE, -70PSF REQUIRES 4" SPACING, SEE CHART ON
 SHEET 10. THIS COMMENT APPLIES TO OTHER OPENINGS.
 PLEASE CHECK ALL AND REVISE INSTALLATION SCHEDULE AS
 REQUIRED.
  
 REVIEW #3 - COMMENT FROM REVIEW #2 PARTIALLY ADDRESSED
 - SOME OPENINGS (SUCH AS OPENING 1) SPECIFY DIFFERENT
 ANCHOR SPACING FOR TOP AND BOTTOM ALTHOUGH BOTH
 CONNECTIONS HAVE THE SAME CONNECTION TYPE, WIND DESIGN
 PRESSURE, AND SPAN. SEE OPENING 1, 12" SPACING DOES NOT
 MEET THE REQUIREMENT OF THE PRODUCT APPROVAL FOR 34"
 SPAN, 2.5" EDGE DISTANCE, BLOCK SUBSTRATE.
  
 PLEASE REVISE. PLEASE HAVE THE QUALIFIER VERIFY
 ACCURACY OF INSTALLATION SCHEDULE PRIOR TO SUBMITTAL.
  
  
  
  
  