Plan Review Notes For Permit 11020296 |
Permit Number |
11020296 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2011-03-14 10:25:36 | ****PROVISO**** | | ****REVISION REQURED**** | | ****ISSUED AT CONTRACTOR'S RISK**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. (2ND REVIEW COMMENT) - THE ANCHOR SPACING DOES NOT | | COMPLY WITH REQUIREMENTS OF THE PRODUCT APPROVAL. FOR | | INSTANCE, SEE OPENING 1. C2 CONNECTION TYPE, BLOCK | | SUBSTRATE, -70PSF REQUIRES 4" SPACING, SEE CHART ON | | SHEET 10. THIS COMMENT APPLIES TO OTHER OPENINGS. | | PLEASE CHECK ALL AND REVISE INSTALLATION SCHEDULE AS | | REQUIRED. | | | | 3RD REVIEW - SOME ITEMS ON THE INSTALLATION SCHEDULE | | HAVE BEEN REVISED, BUT OTHERS HAVE NOT AND DO NOT | | COMPLY WITH THE ANCHOR SCHEDULE. FOR INSTANCE, OPENING | | 1, TOP STILL STATES THAT ANCHOR SPACING PROPOSED IS 12" | | WITH C2 CONNECTION TYPE AND BLOCK SUBSTRATE. | | | | REVISE ANCHOR SPACING TO COMPLY WITH THE REQUIREMENTS | | OF THE PRODUCT APPROVAL. | | | | |
|