Plan Review Notes
Plan Review Notes For Permit 11020296
Permit Number 11020296
Review Stop B
Sequence Number 3
Notes
Date Text
2011-03-14 10:25:36****PROVISO****
 ****REVISION REQURED****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. (2ND REVIEW COMMENT) - THE ANCHOR SPACING DOES NOT
 COMPLY WITH REQUIREMENTS OF THE PRODUCT APPROVAL. FOR
 INSTANCE, SEE OPENING 1. C2 CONNECTION TYPE, BLOCK
 SUBSTRATE, -70PSF REQUIRES 4" SPACING, SEE CHART ON
 SHEET 10. THIS COMMENT APPLIES TO OTHER OPENINGS.
 PLEASE CHECK ALL AND REVISE INSTALLATION SCHEDULE AS
 REQUIRED.
  
 3RD REVIEW - SOME ITEMS ON THE INSTALLATION SCHEDULE
 HAVE BEEN REVISED, BUT OTHERS HAVE NOT AND DO NOT
 COMPLY WITH THE ANCHOR SCHEDULE. FOR INSTANCE, OPENING
 1, TOP STILL STATES THAT ANCHOR SPACING PROPOSED IS 12"
 WITH C2 CONNECTION TYPE AND BLOCK SUBSTRATE.
  
 REVISE ANCHOR SPACING TO COMPLY WITH THE REQUIREMENTS
 OF THE PRODUCT APPROVAL.
  
  