Plan Review Notes For Permit 11020296 |
Permit Number |
11020296 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2011-03-01 14:49:50 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. THE ANCHOR SPACING DOES NOT COMPLY WITH REQUIREMENTS | | OF THE PRODUCT APPROVAL. FOR INSTANCE, SEE OPENING 1. | | C2 CONNECTION TYPE, BLOCK SUBSTRATE, -70PSF REQUIRES 4" | | SPACING, SEE CHART ON SHEET 10. THIS COMMENT APPLIES TO | | OTHER OPENINGS. PLEASE CHECK ALL AND REVISE | | INSTALLATION SCHEDULE AS REQUIRED. | | |
|