Plan Review Notes For Permit 11020284 |
Permit Number |
11020284 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-02-15 09:05:41 | SPECIFY HOW THE NEW SERVICE WILL BE SUPPORTED. NEC | | 110.13 | | SPECIFY THE MINIMUM CLEARANCE REQUIRED FOR THE OVERHEAD | | CONDUCTORS. NEC 230.24 | | SPECIFY THE ENCLOSURE TYPE (OUTDOOR USAGE), VOLTAGE, | | AND INTERRUPTING RATING REQUIRED FOR THE SERVICE. NEC | | 110.11, 110.9, 110.20 | | BUILDING # 1 REQUIRES A SUB PANEL. NEC 225.30 | | PROVIDE GFCI PROTECTION ON RECEPTACLES. NEC 210.8 | | | | ROBERT LECKY, ELECTRICAL PLAN REVIEW, 561-805-6718 | | | | |
|