Plan Review Notes
Plan Review Notes For Permit 11020284
Permit Number 11020284
Review Stop E
Sequence Number 1
Notes
Date Text
2011-02-15 09:05:41SPECIFY HOW THE NEW SERVICE WILL BE SUPPORTED. NEC
 110.13
 SPECIFY THE MINIMUM CLEARANCE REQUIRED FOR THE OVERHEAD
 CONDUCTORS. NEC 230.24
 SPECIFY THE ENCLOSURE TYPE (OUTDOOR USAGE), VOLTAGE,
 AND INTERRUPTING RATING REQUIRED FOR THE SERVICE. NEC
 110.11, 110.9, 110.20
 BUILDING # 1 REQUIRES A SUB PANEL. NEC 225.30
 PROVIDE GFCI PROTECTION ON RECEPTACLES. NEC 210.8
  
 ROBERT LECKY, ELECTRICAL PLAN REVIEW, 561-805-6718
  
  