2011-03-01 10:43:202007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO COPIES OF THE EQUIPMENT SIZING
 CALCULATIONS REQUIRED BY FBCR M1401.3.
  
 2) THE PRINTED NAME, LICENSE NUMBER AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE MECHANICAL DESIGN IS
 REQUIRED TO BE ON THE MECHANICAL DRAWINGS. FS 471 & 481
  
 3) SPECIFY THE SIZES OF THE DUCTS THAT SUPPLY THE
 KITCHEN AND THE POWDER ROOMS ON THE FIRST FLOOR.
  
 4) THE ENERGY COMPLIANCE FORM INDICATES THAT A CREDIT
 WAS TAKEN FOR CEILING FANS. C4.2.1.1 OF THE REVISED
 ENERGY CODE REQUIRES CEILING FANS IN ALL PRIMARY LIVING
 AREAS IN ADDITION TO EACH BEDROOM. THE ELECTRICAL PLAN
 DOES NOT SHOW A CEILING FAN IN THE LIVING ROOM,
 THEREFORE THE CREDIT CAN NOT BE TAKEN. PLEASE CORRECT.
  