2011-03-01 10:43:20 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY MECHANICAL | | | | 1) SUBMIT TWO COPIES OF THE EQUIPMENT SIZING | | CALCULATIONS REQUIRED BY FBCR M1401.3. | | | | 2) THE PRINTED NAME, LICENSE NUMBER AND SIGNATURE OF | | THE PERSON RESPONSIBLE FOR THE MECHANICAL DESIGN IS | | REQUIRED TO BE ON THE MECHANICAL DRAWINGS. FS 471 & 481 | | | | 3) SPECIFY THE SIZES OF THE DUCTS THAT SUPPLY THE | | KITCHEN AND THE POWDER ROOMS ON THE FIRST FLOOR. | | | | 4) THE ENERGY COMPLIANCE FORM INDICATES THAT A CREDIT | | WAS TAKEN FOR CEILING FANS. C4.2.1.1 OF THE REVISED | | ENERGY CODE REQUIRES CEILING FANS IN ALL PRIMARY LIVING | | AREAS IN ADDITION TO EACH BEDROOM. THE ELECTRICAL PLAN | | DOES NOT SHOW A CEILING FAN IN THE LIVING ROOM, | | THEREFORE THE CREDIT CAN NOT BE TAKEN. PLEASE CORRECT. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|