Plan Review Notes For Permit 11020273 |
Permit Number |
11020273 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-02-25 09:55:02 | PROVIDE ONE 20 AMP LAUNDRY CIRCUIT. NEC 210.11 (C) (2) | | PROVIDE A MINIMUM OF TWO 20 AMP KITCHEN CIRCUITS. NEC | | 210.11 (C)(1) | | PROVIDE A 20 AMP BRANCH CIRCUIT TO THE BATHROOMS. NEC | | 210.11 (C)(3) | | PROVIDE A KITCHEN RECEPTACLE AT THE PENINSULAR COUNTER | | TOP. NEC 210.50(C)(3) | | PROVIDE AN INTER SYSTEM BONDING STRIP AT ELECTRIC | | SERVICE. NEC 250.94 | | VERIFY THE AVAILABLE FAULT CURRENT IS LESS THAN 10,000 | | AIC RATED EQUIPMENT. NEC 110.9 | | | | IS THE SELECTED WIRING METHOD TO BE CONDUIT AND CABLE | | OR BOTH? | | PLEASE UPDATE THE PANEL SCHEDULE AND LOAD CALCULATION | | TO REFLECT ALL CHANGES. | | | | ROBERT LECKY, ELECTRICAL PLAN REVIEW, 561-805-6718 | | |
|