Plan Review Notes
Plan Review Notes For Permit 11020273
Permit Number 11020273
Review Stop E
Sequence Number 1
Notes
Date Text
2011-02-25 09:55:02PROVIDE ONE 20 AMP LAUNDRY CIRCUIT. NEC 210.11 (C) (2)
 PROVIDE A MINIMUM OF TWO 20 AMP KITCHEN CIRCUITS. NEC
 210.11 (C)(1)
 PROVIDE A 20 AMP BRANCH CIRCUIT TO THE BATHROOMS. NEC
 210.11 (C)(3)
 PROVIDE A KITCHEN RECEPTACLE AT THE PENINSULAR COUNTER
 TOP. NEC 210.50(C)(3)
 PROVIDE AN INTER SYSTEM BONDING STRIP AT ELECTRIC
 SERVICE. NEC 250.94
 VERIFY THE AVAILABLE FAULT CURRENT IS LESS THAN 10,000
 AIC RATED EQUIPMENT. NEC 110.9
  
 IS THE SELECTED WIRING METHOD TO BE CONDUIT AND CABLE
 OR BOTH?
 PLEASE UPDATE THE PANEL SCHEDULE AND LOAD CALCULATION
 TO REFLECT ALL CHANGES.
  
 ROBERT LECKY, ELECTRICAL PLAN REVIEW, 561-805-6718
  