2011-03-01 16:58:442007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF A SOIL TEST AS REQUIRED BY FBC
 R401.4 FROM A FLORIDA LICENSED GEO-TECHNICAL ENGINEER.
  
 2) PROVIDE TWO COPIES OF A SURFACE WATER DRAINAGE PLAN
 TO SHOW COMPLIANCE WITH FBC R401.3.
  
 3) SHOW COMPLIANCE WITH FBC R309.2 FOR GARAGE
 SEPARATION FROM THE RESIDENCE AND HABITABLE ROOMS
 ABOVE.
  
 4) SHOW COMPLIANCE WITH FBC R502.1.2 FOR DRAFT-STOPPING
 FLOOR/CEILING ASSEMBLIES INTO AREAS OF CONCEALED SPACES
 NOT EXCEEDING 1000 SQFT.
  
 5) SPECIFY THE TRUSS TO WALL CONNECTORS FOR THE UPPER
 AND LOWER ROOFS.
  
 6) THE WALL SECTION ON SHEET 3 SPECIFIES A SIMPSON H-14
 ANCHOR WHICH IS A TRUSS TO WOOD CONNECTOR. THE EXTERIOR
 WALLS ARE MASONRY AT THE FIRST AND SECOND FLOORS.
 PLEASE CORRECT.
  
 7) PROVIDE AN ANCHOR/STRAPPING DETAIL FOR THE WOOD
 FRAMED CHIMNEY.
  
 8) THE ENERGY CALCULATIONS AND THE ELECTRICAL PANEL
 SCHEDULE APPEAR TO INDICATE TWO TANKLESS ELECTRIC WATER
 HEATERS. THE ARCHITECTURAL PLANS DO NOT SPECIFY
 TANKLESS WATER HEATERS. PLEASE CLARIFY.
  
 9) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR THE
 WINDOWS AND DOORS ON THE PLANS. THE WORSE CASE IS THE
 30" OCTAGON WINDOWS LOCATED IN WALL ZONE 5 WITH
 TRIBUTARY AREAS OF LESS THAN 10 SQUARE FEET WITH 140
 MPH WIND-SPEED IN EXPOSURE C WITH A MEAN ROOF HEIGHT OF
 25 FEET.
  
 10) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS AND LISTINGS FOR THE GAS FIREPLACE AND
 FLUE.
  
 11) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 12) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 OVERHEAD GARAGE DOOR THAT WILL BE INSTALLED.
  
 13) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED
 TO INSTALL THE ROOF TILE AND PROVIDE ADEQUATE
 RESISTANCE TO OVERTURNING MOMENT. IF ADHESIVE OR FOAM
 IS USED, SUBMIT THE APPROPRIATE PRODUCT APPROVALS.
  
 14) SUBMIT PRODUCT APPROVALS FOR THE OUT-SWING ENTRY
 DOOR WITH A SIDELITE AS SHOWN ON THE PLANS.
  
 15) SUBMIT PRODUCT APPROVALS FOR THE OUT-SWING GARAGE
 DOOR.
  
 16) PRODUCT APPROVALS WERE SUBMITTED FOR A HORIZONTAL
 SLIDING WINDOW. THERE ARE NO WINDOWS OF THIS TYPE ARE
 SHOWN ON THE PLANS. PLEASE CLARIFY.
  
 17) SUBMIT AN INSTALLATION SCHEDULE FOR THE STORM
 PANELS THAT WILL BE INSTALLED ON THE NON-IMPACT RATED
 DOOR. SPECIFY THE MOUNT TYPE, THE SPAN, THE GLASS
 SEPARATION, THE ANCHOR TYPE, ANCHOR SPACING, EDGE
 DISTANCE AND WALL SUBSTRATE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]