Plan Review Notes For Permit 11020236 |
Permit Number |
11020236 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-02-11 10:44:02 | 101 NORTH CLEMATIS STREET SUITE #100 | | PERMIT #11020236 | | MASTER #10070589 | | REVIEW COMMENTS - FIRE | | | | ADDRESS AND SUITE NUMBER ON THE PLAN SHEET DOES NOT | | MATCH THE ADDRESS ON THE PERMIT APPLICATION. | | | | PER LOCAL CODE AMENDMENTS, DUCT SMOKE DETECTORS SHALL | | INITIATE A GENERAL FIRE ALARM CONDITION. | | | | NO DRAWING SCALE HAS BEEN PROVIDED ON THE PLANS. | | | | MAIN LOUNGE DOES NOT APPEAR TO HAVE SUFFICIENT | | NOTIFICATION APPLIANCES. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | | | | | | | | | | | |
|