2011-02-10 13:41:571700 PALM BEACH LAKES BOULEVARD
 10TH FLOOR RESTROOMS
 PERMIT #11020201
 REVIEW COMMENTS - FIRE
  
 A FIRE ALARM NOTIFICATION APPLIANCE IS REQUIRED TO BE
 LOCATED NOT MORE THAN 15 FEET FROM THE END OF A
 CORRIDOR PER NFPA 72 SECTION 7.5.4.2.5.
  
 FLOOR LEVEL OF WORK NOT INDICATED ON PERMIT APPLICATION
 OR DRAWING TITLE BLOCK.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW