2011-03-01 08:12:53****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PLEASE PROVIDE TWO SETS OF DOCUMENTS FOR PERMIT
 ISSUANCE.
  
 2. PLEASE PROVIDE TWO LEGIBLE COPIES OF THE PRODUCT
 APPROVAL FOR THE SHUTTERS. THE COPIES PROVIDED IS NOT
 COMPLETE (ONLY HALF OF THE SHEETS PRINTED).
  
 3. REGARDING THE INSTALLATION SCHEDULE, PLEASE EXPLAIN
 SPAN AND INSTALLATION. IT STATES THEY WILL BE INSTALLED
 VERTICALLY, BUT THE SPAN DOES NOT CORRELATE WITH THE
 VERTICAL DIMENSION.
  
 4. HOW HAS IT BEEN DETERMINED THAT THE SUBSTRATE IS
 CONCRETE RATHER THAN A FILLED CMU CELL (WHICH WOULD
 REQUIRE USE OF THE CONCRETE BLOCK ANCHOR SPACING)?
  
 5. FOR THE SHUTTER MOUNTING CONNECTION TYPE, PLEASE
 SPECIFY TYPE FROM PRODUCT APPROVAL. THIS SHOULD
 SELECTED FROM OPTIONS C1 THROUGH C5, SEE PRODUCT
 APPROVAL ANCHOR CHARTS AND DETAILS.
  