Plan Review Notes For Permit 11020059 |
Permit Number |
11020059 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2011-03-01 08:12:53 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. PLEASE PROVIDE TWO SETS OF DOCUMENTS FOR PERMIT | | ISSUANCE. | | | | 2. PLEASE PROVIDE TWO LEGIBLE COPIES OF THE PRODUCT | | APPROVAL FOR THE SHUTTERS. THE COPIES PROVIDED IS NOT | | COMPLETE (ONLY HALF OF THE SHEETS PRINTED). | | | | 3. REGARDING THE INSTALLATION SCHEDULE, PLEASE EXPLAIN | | SPAN AND INSTALLATION. IT STATES THEY WILL BE INSTALLED | | VERTICALLY, BUT THE SPAN DOES NOT CORRELATE WITH THE | | VERTICAL DIMENSION. | | | | 4. HOW HAS IT BEEN DETERMINED THAT THE SUBSTRATE IS | | CONCRETE RATHER THAN A FILLED CMU CELL (WHICH WOULD | | REQUIRE USE OF THE CONCRETE BLOCK ANCHOR SPACING)? | | | | 5. FOR THE SHUTTER MOUNTING CONNECTION TYPE, PLEASE | | SPECIFY TYPE FROM PRODUCT APPROVAL. THIS SHOULD | | SELECTED FROM OPTIONS C1 THROUGH C5, SEE PRODUCT | | APPROVAL ANCHOR CHARTS AND DETAILS. | | |
|