Plan Review Notes For Permit 11020032 |
Permit Number |
11020032 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2011-04-06 08:19:45 | PLANS DENIED | | FROM LAST REVIEW FRESH AIR CALCULATIONS WERE NOT ADDED | | TO THE PLANS. | | REFER TO SECTION 13-409.AB.3.3 DAMPER CONTROLS . NEED | | MOTORIZED DAMPERS ON FRESH AIR DUCT . | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|