Plan Review Notes For Permit 11020032 |
Permit Number |
11020032 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-02-23 14:16:47 | FBC PLUMBING 2007 REVIEW #1 | | DENIED: | | | | 1. SHEET A-0.01 SHOWS OCCUPANCY A-3. A MOP SINK WILL BE | | REQUIRED PER PLUMBING TABLE 403.1 | | | | 2. DOMSETIC WATER DIAGRAM IS NOT SIZED. 1" MINIMUM WILL | | BE REQUIRED TO MEN'S/WOMEN'S ROOM TABLE 603.1 | | | | 3. FLOOR DRAINS REQUIRE TRAP PRIMERS. 1002.4 | | | | 4. SANITARY ISO SHOWS 1" TO DF AND KITCHEN SINK- 1 1/2" | | MINIMUM REQUIRED TABLE 710.1 (2) | | | | REVIEW BY LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | (561) 805-6692 | | FAX (561) 653-2692 | | E-MAIL [email protected] | | |
|