Plan Review Notes
Plan Review Notes For Permit 11020032
Permit Number 11020032
Review Stop E
Sequence Number 1
Notes
Date Text
2011-02-23 09:04:30SHOW REQUIRED SAFETY CLEARANCES FOR THE ELECTRIC
 SERVICE. NEC 110.26
 THE AUXILIARY GUTTER FOR THE SERVICE IS UNDER SIZED.
 NEC 366.6, 366.56
 VERIFY THE ELECTRICAL EQUIPMENT HAS SUFFICIENT
 INTERRUPTING RATING. NEC 110.9
 PROVIDE AUTOMATIC LIGHTING CONTROL. FBC 13-415 ABC.1.2
 PROVIDE LIGHTING DENSITY CALCULATION. FBC 13-415 ABC.1
 ON SHEET E-2.01 PROVIDE A PANEL SCHEDULE FOR MAIN # 1.
 PROVIDE AN INTERSYSTEM BONDING BAR AT THE SERVICE. NEC
 250.94
  
 ROBERT LECKY, ELECTRICAL PLAN REVIEW, 561-805-6718
  
  