2011-02-09 15:56:21 | BUILDING PLAN REVIEW |
| PERMIT: 11020032 |
| ADD: 8401 COCOPLUM SOUND LANE |
| CONT: SCHICKEDANZ OAKTON BUILDING GROUP |
| TEL: (561)373-8836 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| ACTION: DENIED |
| |
| 1) THE PERMIT APPLICATION VALUE FOR THE PROJECT IS |
| EXTREMLY LOW AT $39.50 SQ FT. THE BREAK DOWN PROVIDED |
| IS ONLY THE EXTERIOR CONSTRUCTION |
| AND NONE OF THE INTERIOR TRADES WERE INCLUDED. THE ICC |
| BUILDING VALUATION DATA IS WHAT THE CITY USES FOR |
| EXTAMATING CONSTRUCTION COST, |
| THE ESTIMATED COST ARE 4749 SQ FT X $107.62= |
| $511,087.38 . CONSIDERED AS A TYPE VB. II-B $141.28 |
| W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. |
| ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, |
| AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, |
| A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| APPLICABLE GOVERNING AUTHORITY. |
| |
| 108.3* BUILDING PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 2A) THE SURVEY AND FLOOD ZONE CERTIFICATE INDICATE THE |
| FINISH FLOOR OF THE CLUBHOUSE ARE TO BE SET AT 21'-0". |
| |
| 2B) THE SURVEY AND FLOOD ZONE CERTIFICATE INDICATE THE |
| FINISH FLOOR OF THE CLUBHOUSE ARE TO BE SET AT 21'-0". |
| SHEET A-0.01 DOES NOT PROVIDE |
| ANY FURTHER ELEVATIONS OF THE FLOOR OR SURROUNDING |
| WALKWAYS. IT DOES PROVIDE A NOTE INDICATING KNOWLEDGE |
| OF ACCESSIBILITY REQUIREMENTS |
| 11-4.5.2 BUT THE PLANS DOES NOT PROVIDE DESIGN |
| COMPLIANCE WITH THE CODE. PLEASE PROVIDE THE FINISH |
| FLOOR ELEVATIONS, EXTEIOR SIDEWALKS, |
| LANAI AND CURB CUT INFORMATION FOR THE ACCESSIBLE |
| PARKING SPACE AND ACCESSIBLE AISLE. IT IS NOTED PART OF |
| THIS WORK MAY BE ON THE SITE WORK, BUT HAVING A OVER |
| ALL WORKING DRAWING WILL PROVIDE A CLEAR PICTURE FOR |
| CONSTRUCTION AND NOT HAVE CODE VIOLATIONS THAT WILL |
| COST FINANCIALLY AS WELL AS TIME. |
| |
| 3) SHEET A-0.01 BUILDING DESIGN DATA INDICATES THIS |
| BUILDING DESIGN TO BE A TYPE IIB VERSES SHEET S1 |
| INDICATES THE DESIGN TO BE A BUILDING TYPE VB. |
| DISCREPANCY ADDITIONAL INFORMATION REQUIRED. |
| |
| 3A) PLEASE REVIEW 2007/2009 FBC-BUILDING SECTION |
| 603.1(1) FOR TYPE I AND TYPE II CONSTRUCTION FIRE |
| RETARDANT TREATED WOOD MAY BE USED IN: (1.3) ROOF |
| CONSTRUCTION, INCLUDING GIRDERS, TRUSSES, FRAMING AND |
| DECKING. FOR A TYPE II-B BUILDING FOR ROOF SHEATHING |
| THE SHEATHING MUST MEET THE REQUIREMENT FOR FIRE |
| RETARDANT TREATED WOOD. SHEET A5.01 SECTION 2 INDICATES |
| THE USE OF 5/8 INCH PLYWOOD OR 5/8" HUBER ADVAN TECH |
| SHEATHING. SUBMITTED FOR REVIEW IS FL # 5930-R2/ |
| ESR-1473. UNDER THE FL APPROVAL 5930.2 THE REPORT |
| INDICATES THE PANELS ARE LIMITED TO ROOFS ON BUILDING |
| OF TYPE V CONSTRUCTION AND ANY CONSTRUCTION TYPE |
| PERMITED UNDER THE FRC. |
| |
| 3B) PLEASE REVIEW THE ERS-1473 REPORT UNDER CONDITIONS |
| OF USE, 5.4 THE TYPES OF STRUCTURES THESE PANELS CAN BE |
| INSTALLED. |
| |
| 3C) SHEET A5.01INDICATES THERE IS A NAILING SCHEDULE |
| BUT NO SCHEDULE HAS BEEN LOCATED ON EITHER THE A OR S |
| SHEETS. PLEASE INDICATE COMPLIANCE WITH 140 MPH WIND |
| ZONE. 2007/2009 FBC-B 1609.1.1. |
| |
| 4) SHEET S-1 DESIGN PARAMETERS & ASSUMPTIONS WIND |
| DESIGN CRITERIA INDICATE THIS DESIGN AS A "B" EXPOSURE. |
| THE PLAT PLAN INDICATSES TRACT L A DRAINAGE EASEMENT |
| DIRECTLY BEHIND THE BUILDING, WHICH WILL PLACE THIS |
| STRUCTURE INTO AN EXPOSURE "C" TERRAIN. SEE |
| FBC-BUILDING |
| 1609.4.3 EXPOSURE C. OPEN TERRAIN WITH SCATTERED |
| OBSTRUCTIONS, INCLUDING SURFACE UNDULATIONS OR OTHER |
| IRREGULARITIES, HAVING HEIGHTS GENERALLY LESS THAN 30 |
| FEET (9144 MM) EXTENDING MORE THAN 1,500 FEET (457.2 M) |
| FROM THE BUILDING SITE IN ANY QUADRANT. THIS EXPOSURE |
| SHALL ALSO APPLY TO ANY BUILDING LOCATED WITHIN |
| EXPOSURE B-TYPE TERRAIN WHERE THE BUILDING IS WITHIN |
| 100 FEET HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF |
| EXPOSURE C-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET |
| (182.9 M) AND WIDTH GREATER THAN 150 FT. IN THE UPWIND |
| DIRECTION. |
| |
| 4A) SHEET S-1 DESIGN PARAMETERS & ASSUMPTIONS WIND |
| DESIGN CRITERIA INDICATE THE MEAN ROOF HEIGHT OF |
| 15'-0". PLEASE REVIEW DEFINITION FOR MEAN ROOF HEIGHT. |
| MEAN ROOF HEIGHT. THE AVERAGE OF THE ROOF EAVE HEIGHT |
| AND THE HEIGHT TO THE HIGHEST POINT ON THE ROOF |
| SURFACE, EXCEPT THAT EAVE HEIGHT SHALL BE USED FOR ROOF |
| ANGLE OF LESS THAN OR EQUAL TO 10 DEGREES (0.18 RAD). |
| IT APPEARS THE MEAN ROOF HEIGHT IS GREATER THAN 15'-0", |
| IT APPEARS CLOSER TO 17'. PLEASE NOTE THE MULTIPLIERS |
| FOR 17 FEET WILL BE HIGHER WITH A "C" EXPOSURE.ASCE |
| 7-05 FIGURE 6-2. |
| |
| 4B) WITH THE WIND DEISIGN CHANGING FROM A B TO C AND |
| THE MEAN ROOF HEIGHT INCREASING THE MULTIPLYING FACTORS |
| WILL BE 1.29 PLEASE UPDATE WIND DESIGN LEGEND WITH |
| APPROPRIATE FACTORS. ASCE 7-05 FIGURE 6-2. |
| |
| 5) PLEASE PROVIDE COMPLIANCE WITH 2007/ 2009 |
| FBC-BUILDING 1203.2 ENCLOSED ATTICS. |
| |
| 6) PLEASE PROVIDE COMPLIANCE WITH 2007/ 2009 |
| FBC-BUILDING 1209.2 ATTIC ACCESS. |
| |
| 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| JAMES A. WITMER C.B.O. |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: (561)805-6715 |
| FAX:(561)805-6731 |
| E-MAIL: [email protected] |
| |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |
| |
| |