Plan Review Notes For Permit 11010719
Permit Number 11010719
Review Stop B
Sequence Number 1
Notes
Date Text
2011-02-11 11:44:202007 FBC W/2009 REVISIONS
  
 1) SPECIFY THE LEVEL OF ALTERATION ON THE PLANS. SEE
 2007 FBC EXISTING BUILDING CODE. APPEARS TO BE A LEVEL
 3 ALTERATION.
  
 2) SPECIFY THE DESIGN CRITERIA ON THE PLANS. THIS
 INCLUDES THE BASIC WINDSPEED, EXPOSURE CATEGORY AND
 COMPONENT AND CLADDING PRESSURES FOR THE WINDOWS AND
 DOORS,
  
 3) ASTM C 926 REQUIRES 7/8" THICK STUCCO APPLIED IN
 THREE-COATS WHEN APPLIED VERTICALLY TO A METAL LATH
 OVER A SOLID BASE. PLEASE CORRECT.
  
 4) FBC R703.2 REQUIRES A WATER-RESISTIVE BARRIER TO BE
 APPLIED OVER SHEATHING ON EXTERIOR WALLS. SHOW
 COMPLIANCE.
  
 5) SHOW COMPLIANCE WITH FBC R703.6.3 FOR THE REQUIRED
 BOND BREAK BETWEEN THE STUCCO AND THE WATER-RESISTIVE
 BARRIER.
  
 6) PRODUCT APPROVALS WERE SUBMITTED FOR A NON-IMPACT
 RATED OUT SWING GLAZED DOOR. FBC R301.2.1.2 REQUIRES
 GLAZED OPENINGS TO BE PROTECTED FROM WIND-BORNE DEBRIS.
 SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR STORM
 PANELS. SPECIFY THE MOUNTING METHOD, ANCHOR TYPE AND
 ANCHOR SPACING THAT WILL BE USED.
  
 7) THE PLANS WILL BE REQUIRED TO BE REVIEWED BY PALM
 BEACH COUNTY TO DETERMINE IF ANY IMPACT FEES ARE DUE.
 THE STAMPED PLANS AND A COPY OF THE PAID RECEIPT ARE
 REQUIRED TO BE SUBMITTED TO THE CITY CONSTRUCTION
 SERVICES DEPARTMENT BEFORE THE PERMIT IS ISSUED.
  
 8) SPECIFY HOW THE 2 X 4 PT TOP PLATE WILL BE ATTACHED
 TO THE CONCRETE BEAM IN WALL SECTION A.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]