2011-02-11 11:44:20 | 2007 FBC W/2009 REVISIONS |
| |
| 1) SPECIFY THE LEVEL OF ALTERATION ON THE PLANS. SEE |
| 2007 FBC EXISTING BUILDING CODE. APPEARS TO BE A LEVEL |
| 3 ALTERATION. |
| |
| 2) SPECIFY THE DESIGN CRITERIA ON THE PLANS. THIS |
| INCLUDES THE BASIC WINDSPEED, EXPOSURE CATEGORY AND |
| COMPONENT AND CLADDING PRESSURES FOR THE WINDOWS AND |
| DOORS, |
| |
| 3) ASTM C 926 REQUIRES 7/8" THICK STUCCO APPLIED IN |
| THREE-COATS WHEN APPLIED VERTICALLY TO A METAL LATH |
| OVER A SOLID BASE. PLEASE CORRECT. |
| |
| 4) FBC R703.2 REQUIRES A WATER-RESISTIVE BARRIER TO BE |
| APPLIED OVER SHEATHING ON EXTERIOR WALLS. SHOW |
| COMPLIANCE. |
| |
| 5) SHOW COMPLIANCE WITH FBC R703.6.3 FOR THE REQUIRED |
| BOND BREAK BETWEEN THE STUCCO AND THE WATER-RESISTIVE |
| BARRIER. |
| |
| 6) PRODUCT APPROVALS WERE SUBMITTED FOR A NON-IMPACT |
| RATED OUT SWING GLAZED DOOR. FBC R301.2.1.2 REQUIRES |
| GLAZED OPENINGS TO BE PROTECTED FROM WIND-BORNE DEBRIS. |
| SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR STORM |
| PANELS. SPECIFY THE MOUNTING METHOD, ANCHOR TYPE AND |
| ANCHOR SPACING THAT WILL BE USED. |
| |
| 7) THE PLANS WILL BE REQUIRED TO BE REVIEWED BY PALM |
| BEACH COUNTY TO DETERMINE IF ANY IMPACT FEES ARE DUE. |
| THE STAMPED PLANS AND A COPY OF THE PAID RECEIPT ARE |
| REQUIRED TO BE SUBMITTED TO THE CITY CONSTRUCTION |
| SERVICES DEPARTMENT BEFORE THE PERMIT IS ISSUED. |
| |
| 8) SPECIFY HOW THE 2 X 4 PT TOP PLATE WILL BE ATTACHED |
| TO THE CONCRETE BEAM IN WALL SECTION A. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |