Plan Review Notes For Permit 11010709 |
Permit Number |
11010709 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-01-31 15:37:45 | **PROVISOS** | | | | 1. PAGE M-2.1: EXISTING DUCT SHOWN PENETRATING NEW | | RATED WALL WITHOUT PROTECTION. REVISE PLANS SHOWING HOW | | THIS PENETARTION IS TO BE PROTECTED IN ACCORDANCE WITH | | FBC-M 607.5 AND 607.8. | | | | 2. PAGE M-4.1: FIRE DAMPERS SHALL BE INSTALLED PER | | MANUFACTURER'S INSTALLATION INSTRUCTIONS IN ACCORDANCE | | WITH FBC-M 607.2. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|