Plan Review Notes
Plan Review Notes For Permit 11010709
Permit Number 11010709
Review Stop M
Sequence Number 1
Notes
Date Text
2011-01-31 15:37:45**PROVISOS**
  
 1. PAGE M-2.1: EXISTING DUCT SHOWN PENETRATING NEW
 RATED WALL WITHOUT PROTECTION. REVISE PLANS SHOWING HOW
 THIS PENETARTION IS TO BE PROTECTED IN ACCORDANCE WITH
 FBC-M 607.5 AND 607.8.
  
 2. PAGE M-4.1: FIRE DAMPERS SHALL BE INSTALLED PER
 MANUFACTURER'S INSTALLATION INSTRUCTIONS IN ACCORDANCE
 WITH FBC-M 607.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: