2011-01-31 10:37:41 | BUILDING PLAN REVIEW |
| PERMIT: 11010709 |
| ADD: 777S FLAGLER DR/ 6TH FLOOR COMMON AREAS |
| CONT: BUTLER |
| TEL: (561)832-9700 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) THE ARCHITECTURAL PLANS INDICATE RENOVATIONS TO THE |
| COMMON AREA, RESTROOMS AND COMMON CORRIDORS, PLANS FAIL |
| TO INDICATE COMPLIANCE WITH 2007/ 2009 FL EXIST BLD |
| CODE 703.2.2.SUPPLEMENTAL SHAFT AND FLOOR OPENING |
| ENCLOSURE REQUIREMENTS. WHERE THE WORK AREA ON ANY |
| FLOOR EXCEEDS 50 PERCENT OF THAT FLOOR AREA, THE |
| ENCLOSURE REQUIREMENTS OF SECTION 703.2 SHALL APPLY TO |
| VERTICAL OPENINGS OTHER THAN STAIRWAYS THROUGHOUT THE |
| FLOOR. THE BUILDING OFFICIAL DOUG WISE HAS PROPOSED THE |
| FOLLOWING; IF ANY RECONFIGURATION IS PROPOSED WHICH |
| AFFECTS THE ELEVATOR LOBBY AREA ITSELF, AN ELEVATOR |
| LOBBY, OR COMPLIANCE WITH ONE OF THE SIX (6) EXCEPTIONS |
| LISTED IN THE CODE SHALL BE REQUIRED. |
| |
| 707.14.1 ELEVATOR LOBBY. AN ENCLOSED ELEVATOR LOBBY |
| SHALL BE PROVIDED AT EACH FLOOR WHERE AN ELEVATOR SHAFT |
| ENCLOSURE CONNECTS MORE THAN THREE STORIES. THE LOBBY |
| SHALL SEPARATE THE ELEVATOR SHAFT ENCLOSURE DOORS FROM |
| EACH FLOOR BY FIRE PARTITIONS EQUAL TO THE |
| FIRE-RESISTANCE RATING OF THE CORRIDOR AND THE REQUIRED |
| OPENING PROTECTION. ELEVATOR LOBBIES SHALL HAVE AT |
| LEAST ONE MEANS OF EGRESS COMPLYING WITH CHAPTER 10 AND |
| OTHER PROVISIONS WITHIN THIS CODE. |
| |
| EXCEPTIONS: |
| |
| 1. ENCLOSED ELEVATOR LOBBIES ARE NOT REQUIRED AT THE |
| STREET FLOOR, PROVIDED THE ENTIRE STREET FLOOR IS |
| EQUIPPED WITH AN AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE WITH SECTION 903.3.1.1. |
| |
| 2. ELEVATORS NOT REQUIRED TO BE LOCATED IN A SHAFT IN |
| ACCORDANCE WITH SECTION 707.2 ARE NOT REQUIRED TO HAVE |
| ENCLOSED ELEVATOR LOBBIES. |
| |
| 3. WHERE ADDITIONAL DOORS ARE PROVIDED AT THE HOISTWAY |
| OPENING IN ACCORDANCE WITH SECTION 3002.6. SUCH DOORS |
| SHALL BE TESTED IN ACCORDANCE WITH UL 1784 WITHOUT AN |
| ARTIFICIAL BOTTOM SEAL. |
| |
| 4. IN OTHER THAN GROUP I-3, AND BUILDINGS HAVING |
| OCCUPIED FLOORS LOCATED MORE THAN 75 FEET (22 860 MM) |
| ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE |
| ACCESS, ENCLOSED ELEVATOR LOBBIES ARE NOT REQUIRED |
| WHERE THE BUILDING IS PROTECTED BY AN AUTOMATIC |
| SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION |
| 903.3.1.1 OR 903.3.1.2. |
| |
| 5. SMOKE PARTITIONS SHALL BE PERMITTED IN LIEU OF FIRE |
| PARTITIONS TO SEPARATE THE ELEVATOR LOBBY AT EACH FLOOR |
| WHERE THE BUILDING IS EQUIPPED THROUGHOUT WITH AN |
| AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH |
| SECTION 903.3.1.1 OR 903.3.1.2. |
| |
| 6. ENCLOSED ELEVATOR LOBBIES ARE NOT REQUIRED WHERE THE |
| ELEVATOR HOISTWAY IS PRESSURIZED IN ACCORDANCE WITH |
| SECTION 707.14.2. |
| |
| 707.14.2 ENCLOSED ELEVATOR LOBBY PRESSURIZATION |
| ALTERNATIVE. WHERE ELEVATOR HOISTWAY PRESSURIZATION IS |
| PROVIDED IN LIEU OF REQUIRED ENCLOSED ELEVATOR LOBBIES, |
| THE PRESSURIZATION SYSTEM SHALL COMPLY WITH THIS |
| SECTION. |
| |
| 2) SHEET A-1.0 DETAIL# 3 INDICATES A NEW WALL SECTION |
| AND DOOR BUT NO WALL OR DOOR RATING HAS BEEN PROVIDED. |
| PLEASE REVIEW SECTION |
| 2007/ 2009 FBC-B 708.1(1) THE TENANT WALL SEPERATES THE |
| TENANCY FROM THE COMMON AREA OR OTHER TENANTS, |
| REQUIRING A ONE HOUR FIRE RATING FOR THE WALL AND A 20 |
| MINUTE RATING FOR THE DOOR (2007/ 2009 FBC-B TABLE |
| 715.4). |
| |
| 3) PLEASE PROVIDE STENCILING PER 2007/2009 FBC-B 712.6 |
| FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE |
| BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL |
| REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE |
| EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR |
| STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY |
| HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE |
| ANY DECORATIVE CEILING AND IN CONCEALED SPACES. |
| SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE |
| AND SMOKE BARRIER - PROTECT ALL OPENINGS." |
| |