Plan Review Notes For Permit 11010591 |
Permit Number |
11010591 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-01-31 15:07:02 | DENIED BY PLUMBING | | | | 1) SUBMIT SPECIFICATIONS FOR THE 1 HP PUMP THAT WILL BE | | INSTALLED. | | | | 2) THE PUMP CURVE CHART ON SHEET 2 APPEARS TO INDICATE | | A FLOW RATE OF 89 GPM AT A TDH OF 50. SUBMIT THE TDH | | CALCULATIONS SHOWING HOW THE 50 FEET OF HEAD WAS | | DETERMINED. OTHERWISE, THE MAXIMUM FLOW RATE OF THE | | PUMP WILL BE USED. THIS WOULD BE 112 GPM FOR PUMP CURVE | | G ON SHEET 2. | | | | 3) ON SHEET 2 THE SUCTION PIPING IS SHOWN AS 2". AT 89 | | GPM THE FLOW RATE IN 2" PIPE IS MORE THAN THE 8 FEET | | PER SECOND ALLOWED BY CODE SECTION FBC R4101.6.3. | | PLEASE CORRECT. | | | | 4) IF THE MAXIMUM CAPACITY OF THE PUMP OF 112 GPM IS | | USED THE FLOW RATE IN THE 2" RETURN PIPES EXCEED THE 10 | | FEET PER SECOND ALLOWED BY CODE. PLEASE CORRECT. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|