Plan Review Notes
Plan Review Notes For Permit 11010508
Permit Number 11010508
Review Stop M
Sequence Number 1
Notes
Date Text
2011-02-10 14:25:07DENIED BY MECHANICAL
  
 1) THE SCOPE OF WORK STATES SERVICE A/C AND ADD AN A/C
 DUCT TO ONE OF THE BATHROOMS. THE PLANS INDICATE THAT
 DUCTWORK IS BEING ADDED TO THE MASTER BEDROOM. PLEASE
 CLARIFY.
  
 2) IF THE EXISTING AIR HANDLER AND CONDENSING UNIT ARE
 BEING REPLACED AS AN EXACT CHANGEOUT, FILL OUT THE
 CONSTRUCTION SERVICES CHANGE OUT FORM.
  
 3) IF A/C IS BEING INSTALLED FOR THE FIRST TIME, SUBMIT
 EQUIPMENT SIZING CALCULATIONS AND PLANS SHOWING THE
 LOCATION OF THE AIRHANDLER AND CONDENSING UNIT, THE
 SIZE OF ALL DUCT WORK AND GRILLS, THE CFMS AT EACH
 DROP, THE EQUIPMENT SIZES AND MODEL NUMBERS. SHOW
 COMPLIANCE WITH FBCR M1602.4 FOR BALANCED RETURN AIR.
  
 4) IF YOU ARE ADDING DUCTS TO AN EXISTING SYSTEM,
 SPECIFY THE DUCT AND GRILL SIZES AND LOCATIONS AND THE
 CFMS AT THE DROPS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW