Plan Review Notes
Plan Review Notes For Permit 11010463
Permit Number 11010463
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-01-27 12:44:421/27/11 PLANS REVIEWED BY FIRE
  
 1. FIRE ENGINEER ON MASTER PERMIT APPLICATION SHOWS
 RICKY TERRELL P.E. IF HE IS NO LONGER THE P.E. SUBMIT
 NEW PLANS WITH THE CURRENT P.E.
  
 2. APPEARS THE DRAWINGS SUBMITTED ARE IDENTICAL TO THE
 ORIGINAL CONSTRUCTIONS DOCUMENTS REF #09070775.
  
 3. PROVIDE SPRINKLER HEAD LEGEND WITH MAKE, MODEL,
 QUANTITY.
  
 4. PROVIDE SPRINKLER SYMBOL CLARIFICATION
  
 5. PROVIDE SHOP DRAWINGS
  
 6. PROVIDE HYDRALIC CALCULATIONS
  
 7. PROVIDE CURRENT FLOW TEST RESULTS
  
 ***DENIED***
  
 CAPTAIN DANIELS
 BUREAU OF FIRE PREVENTION