Plan Review Notes
Plan Review Notes For Permit 11010333
Permit Number 11010333
Review Stop E
Sequence Number 1
Notes
Date Text
2011-01-21 12:07:42APPROVED WITH PROVISO ON PLANS.
  
 PROVIDE A BONDING BAR AT THE SERVICE. NEC 250.94
 AT LEAST ONE WALL SWITCHED-CONTROLLED LIGHTING OUTLET
 SHALL BE INSTALLED IN EVERY HABITABLE ROOM. NEC 210.70
 RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT ALONG
 THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A
 RECEPTACLE OUTLET. NEC 210.52 (A)(2).
 ADDITIONAL RECEPTACLES ARE REQUIRED FOR ANY WALL SPACE
 MORE THAN 2 FEET IN WIDTH. NEC 210.52 (A) (2).
 BEDROOM RECEPTACLES MUST BE PROTECTED WITH AFCI'S. NEC
 210.12
 THE SMOKE DETECTORS MUST BE INTERCONNECTED. FBC R313.2
 GFCI PROTECTION IS REQUIRED FOR RECEPTACLES IN
 KITCHENS. NEC 210.8
  
 ROBERT LECKY, ELECTRIC PLANS EXAMINER, 561-805-6718
  