Date |
Text |
2011-01-18 10:34:23 | RESIDENTIAL (R3) GARAGE CONVERSION BUILDING REVIEW |
| CHECKLIST. |
| 2007 FBC WITH 2009 REVISIONS. |
| |
| 1- PLANS PROVIDED NEED TO PROVIDE COMPLIANCE WITH THE |
| EMERGENCY EGRESS REQUIREMENTS OF SEC. R310.1 OF 2007 |
| FLORIDA RESIDENTIAL CODE. |
| |
| 2- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW. |
| VALUE NEED TO INCLUDE ALL LABOR AND MATERIALS TO BUILD |
| THE BEDROOM, THE BATHROOM AND THE CLOSET. SEC. 108.3 |
| CITY AMENDMENTS TO FBC. |
| |
| 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| FLORIDA STATUTE. |
| ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| UP. |
| |
| 4- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH |
| COUNTY (2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE |
| DUE. BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT |
| IF FEES ARE DUE. |
| |
| 5- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| N1100.0 OF CHAPTER 11 OF 2007 FLORIDA RESIDENTIAL CODE. |
| ***NOTE: MAKE SURE CORRECT UPDATED FORM IS PROVIDED. |
| COMPLETE ALL THE INFORMATION ON THE FORM. AND, MAKE |
| SURE ALL SIGNATURES ARE PROVIDED AT THE BOTTOM OF THE |
| FORM USED. |
| |
| 6- SPECIFY ON PLANS INSULATION ON EXTERIOR WALLS AND |
| CEILING. CHANGING USE FROM GARAGE TO BEDROOM. THEREFORE |
| EXISTING WALLS AND CEILING MAY NEED TO ADD THE REQUIRED |
| INSULATION. |
| |
| 7- SPECIFY SAFETY GLASS IN SHOWER AREA AS REQUIRED BY |
| SEC. R308.4 OF 2007 FLORIDA RESIDENTIAL CODE. |
| |
| 8- SPECIFY TWO LAYERS OF VAPOR BARRIER AS REQUIRED BY |
| SEC. R703.6.3 2007 FLORIDA RESIDENTIAL CODE. |
| |
| 9- SPECIFY STUCCO THICKNESS AS REQUIRED BY TABLE |
| R702.1(1) 2007 FLORIDA RESIDENTIAL CODE. 5/8" MIN. |
| REQUIRED. |
| |
| 10- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| DCA RULE 9B-72 FOR: |
| A) NEW WINDOWS. COORDINATE WITH ITEM #1 ABOVE. |
| |
| B) SHUTTERS. IF WINDOWS DON'T HAVE IMPACT GLASS. AND |
| PROVIDE SHUTTERS COMPLETE INSTALLATION SCHEDULE. |
| SPECIFY ON SHUTTERS DRAWINGS SPECIFIC MOUNTING |
| CONDITIONS AND ANCHOR TYPE AND SPACING TO BE USED. |
| |
| 11- SPECIFY ON PLANS THE VENTILATION AND LIGHT REQUIRED |
| FOR THE BATHROOM BY SEC. R303.3 OF 2007 FLORIDA |
| RESIDENTIAL CODE. |
| |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561)805-6712 |