Plan Review Notes
Plan Review Notes For Permit 11010294
Permit Number 11010294
Review Stop B
Sequence Number 1
Notes
Date Text
2011-01-18 10:34:23RESIDENTIAL (R3) GARAGE CONVERSION BUILDING REVIEW
 CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PLANS PROVIDED NEED TO PROVIDE COMPLIANCE WITH THE
 EMERGENCY EGRESS REQUIREMENTS OF SEC. R310.1 OF 2007
 FLORIDA RESIDENTIAL CODE.
  
 2- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW.
 VALUE NEED TO INCLUDE ALL LABOR AND MATERIALS TO BUILD
 THE BEDROOM, THE BATHROOM AND THE CLOSET. SEC. 108.3
 CITY AMENDMENTS TO FBC.
  
 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 4- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT
 IF FEES ARE DUE.
  
 5- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.0 OF CHAPTER 11 OF 2007 FLORIDA RESIDENTIAL CODE.
 ***NOTE: MAKE SURE CORRECT UPDATED FORM IS PROVIDED.
 COMPLETE ALL THE INFORMATION ON THE FORM. AND, MAKE
 SURE ALL SIGNATURES ARE PROVIDED AT THE BOTTOM OF THE
 FORM USED.
  
 6- SPECIFY ON PLANS INSULATION ON EXTERIOR WALLS AND
 CEILING. CHANGING USE FROM GARAGE TO BEDROOM. THEREFORE
 EXISTING WALLS AND CEILING MAY NEED TO ADD THE REQUIRED
 INSULATION.
  
 7- SPECIFY SAFETY GLASS IN SHOWER AREA AS REQUIRED BY
 SEC. R308.4 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 8- SPECIFY TWO LAYERS OF VAPOR BARRIER AS REQUIRED BY
 SEC. R703.6.3 2007 FLORIDA RESIDENTIAL CODE.
  
 9- SPECIFY STUCCO THICKNESS AS REQUIRED BY TABLE
 R702.1(1) 2007 FLORIDA RESIDENTIAL CODE. 5/8" MIN.
 REQUIRED.
  
 10- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) NEW WINDOWS. COORDINATE WITH ITEM #1 ABOVE.
  
 B) SHUTTERS. IF WINDOWS DON'T HAVE IMPACT GLASS. AND
 PROVIDE SHUTTERS COMPLETE INSTALLATION SCHEDULE.
 SPECIFY ON SHUTTERS DRAWINGS SPECIFIC MOUNTING
 CONDITIONS AND ANCHOR TYPE AND SPACING TO BE USED.
  
 11- SPECIFY ON PLANS THE VENTILATION AND LIGHT REQUIRED
 FOR THE BATHROOM BY SEC. R303.3 OF 2007 FLORIDA
 RESIDENTIAL CODE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712