 PERMIT #11010251
 REVIEW COMMENTS - FIRE
  
 VERIFY 16-INCHES OF HORIZONTAL DISTANCE EXISTS BETWEEN
 FRYER AND SURFACE FLAMES OF RANGE. IF 16-INCHES CANNOT
 BE ENSURED, A STEEL BAFFLE AT LEAST 8-INCHES IN HEIGHT
 IS REQUIRED TO SEPARATE THE GREASE FROM OPEN FLAMES.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW