 REVIEW COMMENTS - FIRE
  
  
 FIRE SPRINKLER DOCUMENTS ARE REQUIRED TO BE SEALED BY A
 PROFESSIONAL ENGINEER WHEN 50 OR MORE FIRE SPRINKLERS
 ARE ADDED, DELETED OR ALTERED PER SECTION 105.3.1.2(2)
 OF THE FLORIDA BUILDING CODE.
  
 REVISE PERMIT APPLICATION TO REFLECT CORRECT NUMBER OF
 SPRINKLERS AND ADJUST JOB VALUE.
  
 SECOND FLOOR NORTH: PROVIDE SPRINKLER COVERAGE FOR
 SMALL CORNER AREA EAST OF STORAGE ROOM 4.
  