2011-01-14 11:30:05 | 205 DATURA STREET | | PERMIT #11010175 | | MASTER #10080641 | | REVIEW COMMENTS - FIRE | | | | | | FIRE SPRINKLER DOCUMENTS ARE REQUIRED TO BE SEALED BY A | | PROFESSIONAL ENGINEER WHEN 50 OR MORE FIRE SPRINKLERS | | ARE ADDED, DELETED OR ALTERED PER SECTION 105.3.1.2(2) | | OF THE FLORIDA BUILDING CODE. | | | | REVISE PERMIT APPLICATION TO REFLECT CORRECT NUMBER OF | | SPRINKLERS AND ADJUST JOB VALUE. | | | | SECOND FLOOR NORTH: PROVIDE SPRINKLER COVERAGE FOR | | SMALL CORNER AREA EAST OF STORAGE ROOM 4. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW |
|