2011-01-14 12:16:09MECHANICAL PROVISO
  
 FBCR M1602.4 REQUIRES THE RETURN TRANSFER DUCTS TO BE
 ONE AND ONE HALF THE CROSS SECTIONAL AREA OF THE SUPPLY
 DUCT ENTERING THE ROOM OR SPACE. THE SUPPLY TO THE
 MASTER BEDROOM INCLUDES THE BATHROOM.
  
  