 PERMIT #11010168
 REVIEW COMMENTS - FIRE
  
 THE COMBINED OCCUPANT LOAD IS SHOWN AS 69 OCCUPANTS;
 DOORS ARE REQUIRED TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL FOR AN OCCUPANT LOAD OF 50 OR GREATER PERSONS
 PER SECTION 7.2.1.4.2 OF THE FLORIDA FIRE PREVENTION
 CODE (NFPA 101 - LIFE SAFETY CODE).
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER???PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER. (REFERENCE: SECTION 8.3.2.4 OF FLORIDA
 FIRE PREVENTION CODE ??? NFPA 101)
  
 PROVIDE NEW AND EXISTING DOOR HARDWARE/SECURITY
 INFORMATION ON PLANS.
  
 PROVIDE VISUAL NOTIFICATION APPLIANCE IN CONFERENCE
 ROOM 101.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  