Date |
Text |
2011-05-31 09:33:20 | ****CORRECTIONS**** |
| |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2007 |
| FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| |
| COMMENTS FROM PREVIOUS LIST, NOT ADDRESSED. |
| |
| 1. ADDRESSED. |
| |
| 2. PROVIDE CALCULATIONS FOR THE ALUMINUM I BEAMS TO |
| SHOW RESISTANCE TO WIND, DEAD AND LIVE LOADS FBC R301. |
| |
| 3. SEE PREVIOUS LIST, ON THE FLOOR PLAN PROVIDE ROOM |
| DESIGNATION FOR THE ADJACENT ROOMS WHICH OPEN INTO THE |
| EXISTING PORCH (BY EITHER WINDOW OR DOOR). IF BEDROOMS |
| ARE AFFECTED, SHOW ALTERNATE COMPLIANCE WITH EMERGENCY |
| MEANS OF ESCAPE REQUIREMENTS, FBC R310. |
| |
| 4. IT APPEARS THAT A PORTION OF TH PORCH WALL IS A |
| TENANT SEPARATION WALL. A FIRE RATED WALL IS REQUIRED. |
| SHOW TENANT SEPARATIONS ON THE PLAN, FBC R317 AND |
| PROVIDE A DETAIL FOR THE NEW TENANT SEPARATION WALL |
| WHICH IS NOW REQUIRED (NEW STORAGE ROOM AND EXISTING |
| TENANT SEPARATION). |
| |
| 5. SHOW TRAVEL TO EXIT, FBC CHAPTER 3. IT IS NOT CLEAR |
| THROUGH WHAT ADJACENT ROOMS AN OCCUPANT IS REQUIRED TO |
| TRAVEL THROUGH IN ORDER TO REACH AN EXIT. |
| |
| 6. ADDRESSED. |
| |
| 7. COMMENT FROM PREVIOUS LISTS - THIS PARCEL IS LOCATED |
| IN A HIGH HAZARD FLOOD ZONE, A9. THE MINIMUM FLOOR |
| ELEVATION REQUIRED IS 13'6". OUR RECORDS SHOW THAT THE |
| EXISTING STRUCTURE HAS AN ELEVATION OF APPROXIMATELY |
| 12', BUT A 6" STEP DOWN IS PROPSED. SEE NFIP |
| REQUIREMENTS FOR ADDITIONS, PROPOSED NEW HABITABLE |
| SPACE IS TO BE A MINIMUM OF 6" ABOVE BASE FLOOD |
| ELEVATION PER CITY OF WEST PALM BEACH MUNICIPAL CODE |
| 94-546(B). |
| |
| REVIEW 3 - PLAN HAS BEEN REVISED TO SHOW A STORAGE AREA |
| RATHER THAN HABITABLE SPACE. FLOOD VENTS ARE NOW SHOWN. |
| PLEASE PROVIDE ELEVATION CERTIFICATE (SEE COMMENT #23) |
| WHICH SHOULD SHOW COMPLIANCE FOR FLOOD VENTS. SEE THE |
| FEMA/NFIP WEBSITE FOR MORE INFORMATION. |
| |
| HTTP://WWW.FEMA.GOV/LIBRARY/FILE?TYPE=PUBLISHEDFILE&FIL |
| E=FEMA_TB_1__1_.PDF&FILEID=CB212200-A517-11DD-B825-0011 |
| 85636A87 |
| |
| 8. PROVIDE A COPY OF A SURVEY WHICH SHOWS DISTANCE OF |
| PROPOSED NEW ROOM TO PROPERTY LINES. |
| |
| 9. ADDRESSED. |
| |
| 10. THIS PARCEL HAS AN EXPIRED PERMIT 03121693, PLEASE |
| ADDRESS. |
| |
| 11-13. ADDRESSED. |
| |
| 14. PROVIDE MORE INFORMATION REGARDING THE EXISTING |
| ROOF PANELS. PORCHES CAN BE DESIGNED WITH AN IMPORTANCE |
| FACTOR OF .77, NOT CLEAR IF THE EXISTING ROOF STRUCTURE |
| CAN MEET REQUIREMENT FOR HABITABLE SPACE WITH AN |
| IMPORTANCE FACTOR OF 1.0. |
| |
| 15. PROVIDE OVER HEAD DOOR PRODUCT APPROVAL. |
| |
| 16. BOND BREAK REQUIRED, FBC R 703.6.3. |
| |
| 17. SPECIFY SILL PLATE (SIZE AND MATERIAL). PT |
| REQUIRED. |
| |
| 18. FRAMING DETAIL CONFLICTS WITH OTHER DETAILS; |
| FRAMING DETAIL SHOWS A WOOD FRAME WALL BUT OTHER |
| DETAILS SHOW A CONCRETE BLOCK KNEE WALL. FBC 106. |
| |
| 19. HOW HAS IT BEEN DETERMINED THAT THERE ARE EXISTING |
| FILLED CELLS ON EACH SIDE OF EACH PROPOSED NEW DOOR AND |
| WINDOW INSTALLATION? EITHER PROVIDE INFORMATION |
| REGARDING HOW THIS HAS BEEN DETERMINED OR PROVIDE A |
| DETAIL FOR THE NEW FILLED CELLS. |
| |
| 3RD REVIEW, PLEASE PROVIDE PLANS AND PERMIT NUMBER FOR |
| THE EXISTING PORCH. EXISTING CONDITIONS NOT CLEAR. |
| |
| 20. ADDRESSED. |
| |
| 21. PROVIDE A COST BREAKDOWN FOR THIS PROJECT. |
| |
| 22. IT IS NOT CLEAR HOW THE ROOF IS SUPPORTED BY A KNEE |
| WALL, NO COLUMNS SHOWN. PROVIDE MORE INFORMATION. |
| |
| 3RD REVIEW, SEE COMMENT #19. |
| |
| 23. PROVIDE A PROPERLY COMPLETED ELEVATION CERTIFICATE |
| (CONSTRUCTION DRAWINGS). HTTP://WWW.FEMA.GOV/PLAN/PREVE |
| NT/FLOODPLAIN/NFIPKEYWORDS/ELEVATION_CERTIFICATE.SHTM |
| |