2011-01-12 14:04:411 HARVARD CIRCLE, SUITE #102
 PERMIT #11010118
 REVIEW COMMENTS - FIRE
  
 FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION
 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES
 SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE
 DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE
 SPRINKLERS. NOTE: SEPARATE PLANS AND PERMITS ARE
 REQUIRED FOR THE INSTALLATION OF THE FIRE SPRINKLER
 SYSTEM AND FIRE ALARM SYSTEM.
  
 THE PLANS SHOW DOORS WITH EXISTING CARD-READER ACCESS.
 INDICATE HOW EGRESS IS ACHIEVED.
  
 COORDINATE REFLECTED CEILING PLAN AND ELECTRICAL
 DRAWING EXIT SIGN LOCATIONS.
  
 FLUSH BOLTS ARE NOT PERMITTED AT THE TOP AND BOTTOM OF
 THE DOOR LEAF UNLESS THE RELEASING MECHANISM COMPLIES
 WITH SECTION 7.2.1.5.9.1 OF THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION (NFPA 101).
  
 PROVIDE TACTILE SIGNAGE AT EXIT DOOR LOCATIONS.
  
 PER LOCAL CODE AMENDMENTS, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  