2011-01-11 10:20:33****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. MORE INFORMATION REQUIRED TO DETERMINE ZONE,
 FBC1609. CONTRACTOR'S INFORMATION REGARDING LOCATION OF
 OPENING IN ZONE 4 WAS HELPFUL; HOWEVER, BASED ON THE
 FLOOR PLAN AND WRITTEN DESCRIPTION PROVIDED, IT APPEARS
 THAT THE OPENING IS LOCATED IN CLOSE PROXIMITY TO A
 BUILDING CORNER. IT APPEARS THAT THE CONTRACTOR IS
 GIVING DISTANCE TO THE CORNER OF THE BALCONY RATHER
 THAN THE ACTUAL BUILDING CORNER. EITHER REVISE THE PLAN
 TO SHOW DISTANCE FROM THE INTERIOR BALCONY CORNER OR
 HAVE THE ENGINEER DETERMINE ZONE. NOTE THAT SIMPLIFIED
 METHOD OF ASCE7-05 IS RESTRICTED TO RECTANGULAR
 BUILDINGS UNDER 60 FEET, WHICH DOES NOT APPLY IN THIS
 CASE.
  
  