Plan Review Notes For Permit 11010063 |
Permit Number |
11010063 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-01-06 09:36:58 | VISITED THE PROJECT PRIOR TO THIS PLAN REVIEW. THE | | INDICATED WORK ENCOMPASSES AN ISOLATED REPAIR AT UNIT | | #607. THE WINDOW INSTALLER COULD NOT INSTALL THE | | REPLACEMENT WINDOWS DUE TO THE EXISTING CONDITION OF | | THE ADJACENT COLUMNS AND WINDOW SILL. THIS WORK IS | | EMERGENCY CONCRETE REPAIR SINCE THE OPENING WITHIN THE | | MASTER BEDROOM IS CURRENTLY COVERED WITH PLYWOOD. THE | | WORK IS STRUCTURAL AND THEREFORE, PURSUANT TO F.S. | | 553.79(A) A SPECIAL INSPECTOR AGREEMENT MUST BE | | SUBMITTED. | | | | 1) THE CONTRACTOR SHALL ENSURE ALL SAFEGUARDS ARE IN | | PLACE PRIOR TO STARTING WORK: | | | | FEBC, SECTION 1402.2 -MANNER OF REMOVAL. WASTE | | MATERIALS SHALL BE REMOVED IN A MANNER WHICH PREVENTS | | INJURY OR DAMAGE TO PERSONS, ADJOINING PROPERTIES AND | | PUBLIC RIGHTS-OF-WAY | | | | 2) 501.3 CONFORMANCE. THE WORK SHALL NOT MAKE THE | | BUILDING LESS CONFORMING THAN IT WAS BEFORE THE REPAIR | | WAS UNDERTAKEN. | | | | | | | | | | |
|