2011-01-05 14:33:35****PROVISO****
 ****REVISION REQUIRED PRIOR TO FIRST INSPECTION****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SHEET 1 OF 26, DESIGN PRESSURES ARE NOTED AS "TBD."
 ENGINEER IS TO SPECIFY DESIGN PRESSURES, FBC1609, FBC
 EXISTING BUILDING 606.4.
  
 2. SHEET 1 OF 26, PANIC HARDWARE IS EXCLUDED. REVISE
 PLAN TO SHOW CODE COMPLIANCE BY PROVIDING ANY REQUIRED
 INFORMATION (SUCH AS OCCUPANCY, OCCUPANT LOAD, LIFE
 SAFETY PLAN, ETC.). SEE ALSO FBC EXISTING BUILDING
 601.1.
  
 3. ***BUCK INSPECTION REQUIRED*** (INFORMATIONAL)
  
  
  
  
  
  
  