Notes |
Date |
Text |
2011-02-14 11:25:42 | FBC PLUMBING 2007 REVIEW #2 | | DENIED: | | | | 1. WATER COOLER DOES NOT APPEAR TO CONFORM TO THE | | DRINKING FOUNTAIN STANDARDS LISTED IN 410.1 | | 2. WATER COOLERS AND BOTTLED WATER MAY ONLY BE | | SUBSTITUTED FOR 50% OF REQUIRED DRINKING FOUNTAINS. | | | | 410.1 APPROVAL. DRINKING FOUNTAINS SHALL CONFORM TO | | ASME A112.19.1M, ASME A112.19.2M OR ASME A112.19.9M AND | | WATER COOLERS SHALL CONFORM TO ARI 1010. DRINKING | | FOUNTAINS AND WATER COOLERS SHALL CONFORM TO NSF 61, | | SECTION 9. WHERE WATER IS SERVED IN RESTAURANTS, | | DRINKING FOUNTAINS SHALL NOT BE REQUIRED. IN OTHER | | OCCUPANCIES, | | WHERE DRINKING FOUNTAINS ARE REQUIRED, WATER COOLERS OR | | BOTTLED WATER DISPENSERS SHALL BE PERMITTED TO BE | | SUBSTITUTED FOR NOT MORE THAN 50 PERCENT OF THE | | REQUIRED DRINKING FOUNTAINS. | | | | REVIEW BY LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | (561) 805-6692 | | FAX (561) 653-2692 | | E-MAIL [email protected] | | | | | | |
|