Date Text
2011-02-14 11:25:42FBC PLUMBING 2007 REVIEW #2
 DENIED:
  
 1. WATER COOLER DOES NOT APPEAR TO CONFORM TO THE
 DRINKING FOUNTAIN STANDARDS LISTED IN 410.1
 2. WATER COOLERS AND BOTTLED WATER MAY ONLY BE
 SUBSTITUTED FOR 50% OF REQUIRED DRINKING FOUNTAINS.
  
 410.1 APPROVAL. DRINKING FOUNTAINS SHALL CONFORM TO
 ASME A112.19.1M, ASME A112.19.2M OR ASME A112.19.9M AND
 WATER COOLERS SHALL CONFORM TO ARI 1010. DRINKING
 FOUNTAINS AND WATER COOLERS SHALL CONFORM TO NSF 61,
 SECTION 9. WHERE WATER IS SERVED IN RESTAURANTS,
 DRINKING FOUNTAINS SHALL NOT BE REQUIRED. IN OTHER
 OCCUPANCIES,
 WHERE DRINKING FOUNTAINS ARE REQUIRED, WATER COOLERS OR
 BOTTLED WATER DISPENSERS SHALL BE PERMITTED TO BE
 SUBSTITUTED FOR NOT MORE THAN 50 PERCENT OF THE
 REQUIRED DRINKING FOUNTAINS.
  