Plan Review Notes For Permit 10120607 |
Permit Number |
10120607 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-01-07 11:13:39 | GFCI RECEPTACLE REQUIRED OUTSIDE AT THE ENTRANCE AREA | | AND IN THE GARAGE. NEC 210.52 | | GFCI PROTECTION REQUIRED FOR COUNTER TOP RECEPTACLES. | | NEC 210.8, 210.52 | | GFCI PROTECTED RECEPTACLE REQUIRED AT MECHANICAL | | EQUIPMENT. NEC 210.63 | | ALL NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC | | 406.11 | | THE SMOKE DETECTORS MUST BE INTERCONNECTED. FBC R313.2 | | BEDROOM RECEPTACLES MUST BE PROTECTED WITH AFCI'S. NEC | | 210.12 | | PROVIDE A BONDING BAR AT THE SERVICE. NEC 250.94 | | LOCATE ON THE PLAN THE OUTDOOR MECHANICAL EQUIPMENT. | | VERIFY ALL OUTDOOR EQUIPMENT IS ABOVE THE MINIMUM FLOOD | | ELEVATION. | | | | ROBERT LECKY, ELECTRICAL PLANS REVIEW, 561-805-6718 | | | | |
|