Plan Review Notes
Plan Review Notes For Permit 10120607
Permit Number 10120607
Review Stop E
Sequence Number 1
Notes
Date Text
2011-01-07 11:13:39GFCI RECEPTACLE REQUIRED OUTSIDE AT THE ENTRANCE AREA
 AND IN THE GARAGE. NEC 210.52
 GFCI PROTECTION REQUIRED FOR COUNTER TOP RECEPTACLES.
 NEC 210.8, 210.52
 GFCI PROTECTED RECEPTACLE REQUIRED AT MECHANICAL
 EQUIPMENT. NEC 210.63
 ALL NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC
 406.11
 THE SMOKE DETECTORS MUST BE INTERCONNECTED. FBC R313.2
 BEDROOM RECEPTACLES MUST BE PROTECTED WITH AFCI'S. NEC
 210.12
 PROVIDE A BONDING BAR AT THE SERVICE. NEC 250.94
 LOCATE ON THE PLAN THE OUTDOOR MECHANICAL EQUIPMENT.
 VERIFY ALL OUTDOOR EQUIPMENT IS ABOVE THE MINIMUM FLOOD
 ELEVATION.
  
 ROBERT LECKY, ELECTRICAL PLANS REVIEW, 561-805-6718
  
  