2010-12-29 15:23:44600 VILLAGE BOULEVARD
 REVISION #10120590
 PERMIT #10090787
 MASTER #10070434
 REVIEW COMMENTS - FIRE
  
  
 THE UPRIGHT EXTENDED COVERAGE SPRINKLERS (TY6137) WITH
 A K-FACTOR OF 14.0 ARE ONLY UL LISTED FOR STANDARD
 RESPONSE IN THIS APPLICATION; HOWEVER, THE HYDRAULIC
 CALCULATION AREA USES THE AREA REDUCTION METHOD FOR
 QUICK RESPONSE SPRINKLERS.
  
 SUBMITTED DRAWINGS HAVE NOT BEEN SIGNED AND SEALED BY
 AN ENGINEER.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  