2010-12-29 14:05:34 | 1732--45TH STREET | | PERMIT #10120582 | | MASTER #10090025 | | REVIEW COMMENTS - FIRE | | | | | | INDICATE THE HAZARD CLASSIFICATION AND THE DESIGN | | DENSITY OF THE SYSTEM. | | | | INDICATE IF THE EXPOSED STRUCTURE IS CONSIDERED | | OBSTRUCTED OR UNOBSTRUCTED CONSTRUCTION. INDICATE THE | | SPRINKLER DISTANCE BELOW THE ROOF DECK BASED UPON THE | | CONSTRUCTION TYPE (OBSTRUCTED/UNOBSTRUCTED). | | | | THE SPRINKLER LOCATED IN WEST AREA OF THE STOREROOM IS | | PROTECTING AN AREA GREATER THAN 130 SQUARE FEET. | | | | INDICATE THE MAXIMUM STORAGE/DISPLAY HEIGHT THAT IS | | INTENDED FOR THIS RETAIL SPACE. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | |
|