Plan Review Notes For Permit 10120531 |
Permit Number |
10120531 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-12-27 13:34:19 | 5312 BROADWAY | | PERMIT #10120531 | | REVIEW COMMENTS - FIRE | | | | | | PROVIDE SPEAKER/STROBE NOTIFICATION APPLIANCES AS NEW | | ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING | | 300 OCCUPANTS SHALL RECEIVE FIRE ALARM NOTIFICATION BY | | VISIBLE SIGNALS AND VOICE ANNOUNCEMENTS. (REFERENCE: | | SECTION 12.3.4.3.3 OF FLORIDA FIRE PREVENTION CODE ??? | | NFPA 101) | | | | PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE | | INSTRUCTING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED, | | LOCATE THE NEAREST EXIT AND EXIT THE BUILDING | | IMMEDIATELY. | | | | THE TAMPER SWITCHES ON THE FIRE SPRINKLER BACKFLOW | | PREVENTER NEED TO BE MONITORED. | | | | VERIFY A FIRE SPRINKLER EXISTS AT THE TOP OF THE | | ELEVATOR SHAFT, OTHERWISE A SMOKE DETECTOR IS NOT | | PERMITTED IN THIS LOCATION. | | | | PER LOCAL AMENDMENTS, DUCT SMOKE DETECTORS SHALL | | INITIATE A GENERAL FIRE ALARM CONDITION. | | | | NOTE: THE BUILDING PERMIT FOR THIS LOCATION HAS EXPIRED | | (PERMIT NO. 06090243). THE PERMIT CHANGED THE OCCUPANCY | | FROM BUSINESS TO ASSEMBLY. A FIRE ALARM SUB-PERMIT WILL | | NOT BE ISSUED WITHOUT A MASTER BUILDING PERMIT. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | | | |
|