Plan Review Notes
Plan Review Notes For Permit 10120531
Permit Number 10120531
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-12-27 13:34:195312 BROADWAY
 PERMIT #10120531
 REVIEW COMMENTS - FIRE
  
  
 PROVIDE SPEAKER/STROBE NOTIFICATION APPLIANCES AS NEW
 ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING
 300 OCCUPANTS SHALL RECEIVE FIRE ALARM NOTIFICATION BY
 VISIBLE SIGNALS AND VOICE ANNOUNCEMENTS. (REFERENCE:
 SECTION 12.3.4.3.3 OF FLORIDA FIRE PREVENTION CODE ???
 NFPA 101)
  
 PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE
 INSTRUCTING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED,
 LOCATE THE NEAREST EXIT AND EXIT THE BUILDING
 IMMEDIATELY.
  
 THE TAMPER SWITCHES ON THE FIRE SPRINKLER BACKFLOW
 PREVENTER NEED TO BE MONITORED.
  
 VERIFY A FIRE SPRINKLER EXISTS AT THE TOP OF THE
 ELEVATOR SHAFT, OTHERWISE A SMOKE DETECTOR IS NOT
 PERMITTED IN THIS LOCATION.
  
 PER LOCAL AMENDMENTS, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 NOTE: THE BUILDING PERMIT FOR THIS LOCATION HAS EXPIRED
 (PERMIT NO. 06090243). THE PERMIT CHANGED THE OCCUPANCY
 FROM BUSINESS TO ASSEMBLY. A FIRE ALARM SUB-PERMIT WILL
 NOT BE ISSUED WITHOUT A MASTER BUILDING PERMIT.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  
  