Plan Review Notes
Plan Review Notes For Permit 10120524
Permit Number 10120524
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-12-29 11:48:332465 MERCER AVENUE
 PERMIT NUMBER 10120524
 "COMMERCIAL CONSTRUCT INTERIOR IMPROVEMENTS"
  
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODELING.
  
 3. NEW HYDRAULIC CALCULATIONS ARE TO BE SUBMITTED WITH
 THE FIRE SPRINKLER DRAWINGS SINCE FLEX HEADS ARE
 PLANNED TO BE USED.
  
 4. NEW TENANT DEMISING WALLS ARE TO BE PROPERLY
 IDENTIFIED AND LABELED AND ALL PENETRATIONS ARE TO BE
 PROPERLY SEALED.
  
 5. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATION.
  
 6. ACCESS TO A PROPERLY SERVICE TAGGED AND RATED FIRE
 EXTINGUISHER SHALL NOT EXCEED 75 FEET OF TRAVEL
 DISTANCE.
  
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION