Plan Review Notes For Permit 10120524 |
Permit Number |
10120524 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-12-29 11:48:33 | 2465 MERCER AVENUE | | PERMIT NUMBER 10120524 | | "COMMERCIAL CONSTRUCT INTERIOR IMPROVEMENTS" | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | WITH NFPA 241. | | | | 2. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE | | SPRINKLER AND FIRE ALARM REMODELING. | | | | 3. NEW HYDRAULIC CALCULATIONS ARE TO BE SUBMITTED WITH | | THE FIRE SPRINKLER DRAWINGS SINCE FLEX HEADS ARE | | PLANNED TO BE USED. | | | | 4. NEW TENANT DEMISING WALLS ARE TO BE PROPERLY | | IDENTIFIED AND LABELED AND ALL PENETRATIONS ARE TO BE | | PROPERLY SEALED. | | | | 5. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATION. | | | | 6. ACCESS TO A PROPERLY SERVICE TAGGED AND RATED FIRE | | EXTINGUISHER SHALL NOT EXCEED 75 FEET OF TRAVEL | | DISTANCE. | | | | | | APPROVED PROVISO | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION |
|