Plan Review Notes For Permit 10120436
Permit Number 10120436
Review Stop M
Sequence Number 1
Notes
Date Text
2011-01-04 12:05:33PLANS DENIED
 PLANS ARE NOT COMPLETE
 PLEASE PROVIDE DUCT SIZE, EQUIPMENT SCHEDULE AND FRESH
 AIR CALCULATIONS ON THE PLANS.
 PLEASE INDICATE THE PURPOSE OF THE FUME EXTRACTION, IF
 IT IS FOR A NAIL SALON THEN REFER TO TABLE 403.3
 REQUIRED OUTDOOR VENTILATION.
 PLEASE SHOW ON THE PLANS HOW THE NEW R/T IS GETTING
 BACK TO AHU # 1 & 2
 PLAN REVIEW BY HAROLD MOSER 561-805-6732