2011-01-04 08:09:03BUILDING PLAN REVIEW
 PERMIT: 10120436/ 10010151
 ADD: 771 VILLAGE BLVD# 204
 CONT: GREY CONSTRUCTION
 TEL: (561)312-2766
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 REVIEW
 ACTION: DENIED
  
  
 1 CRH DESIGN & DRAFTING IS WORKING OUT OF THE SCOPE OF
 THEIR LICENSE. PLEASE REVIEW
 FLORIDA STATUTE???S 481.229 ARCHITECTURE LICENSING LAWS
 AND EXEMPTIONS. CRH DESIGN
 & DRAFTING CAN NOT DESIGN FOR COMMERCIAL WORK, IF THEY
 SUBMIT ANY WORK TO THIS JURISDICTION IN THE FUTURE IT
 WILL BE TURNED OVER TO THE APPROPRIATE BOARD!
  
 2) SHEET A-2 INDICATES ALL WORK IS EXISTING. PLEASE
 CORRECT, IT IS WORK THAT WAS COMPLETED WITHOUT BENEFIT
 OF PERMITS AND INSPECTIONS AS INDICATED BY LIST OF
 BUILDING CODE VIOLATIONS.
  
 3) PLEASE CORRECT 2 EXISTING COFFER CEILING BY SEPARATE
 PERMIT (10120436), THIS WORK AND PROPOSED REVISION
 (10120436) IS ALL UNDER ONE PERMIT. THE REVISION NUMBER
 (10120436) IS FOR TRACKING PURPOSES ONLY. PLEASE NOTE
 THAT THE DROPPED COFFER CEILINGS NEVER INDICATED AS TO
 THE MINIMUM BUILDING TYPE AND WAS ISSUED WITH EITHER
 WHITE WOOD OR P.T. 2X4 FRAMING MEMBERS. PLEASE REVIEW
 SECTION FBC-B 603.1.1 AND THE USE OF COMBUSTIBLES- FIRE
 RETARDANT TREATED WOOD. PLEASE CORRECT ISSUED PLANS.
  
 4) A-2 THE PROPOSED LEFT HALLWAY INDICATES A WIDTH OF
 3???-7??? WITH 3???0??? DOORS THAT SWING INTO THE
 HALLWAY, PLEASE REVIEW SECTION FBC-B 1005.2 DOOR
 ENCROACHMENT. DOORS OPENING INTO THE PATH OF EGRESS
 TRAVEL SHALL NOT REDUCE THE REQUIRED WIDTH TO LESS THAN
 ONE-HALF DURING THE COURSE OF THE SWING. WHEN FULLY
 OPEN, THE DOOR SHALL NOT PROJECT MORE THAN 7 INCHES
 (178 MM) INTO THE REQUIRED WIDTH. THE MINIMUM WIDTH OF
 A CORRIDOR WITH AN OCCUPANT LOAD OF LESS THAN 50 WOULD
 BE 4???-6???.
  
 5) A-2 THERE ARE OFFICES WITH DOORS AND GLAZING JUST
 ADJACENT TO THE DOORWAY PLEASE INDICATE COMPLIANCE WITH
 FBC-B 2406.3 HAZARDOUS LOCATIONS. THE FOLLOWING SHALL
 BE CONSIDERED SPECIFIC HAZARDOUS LOCATIONS REQUIRING
 SAFETY GLAZING MATERIALS:
 (6.) GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL
 ADJACENT TO A DOOR WHERE THE NEAREST EXPOSED EDGE OF
 THE GLAZING IS WITHIN A 24-INCH (610 MM) ARC OF EITHER
 VERTICAL EDGE OF THE DOOR IN A CLOSED POSITION AND
 WHERE THE BOTTOM EXPOSED EDGE OF THE GLAZING IS LESS
 THAN 60 INCHES (1524 MM) ABOVE THE WALKING SURFACE.
 6) A-2 PLANS ARE CIRCLED IN RED INK (3) LOCATIONS WHERE
 PLANS WILL NEED TO COMPLY WITH
 FBC-B 11-4.13.6 MANEUVERING CLEARENCES AT DOORS.
 MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE NOT
 AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG.
 25. THE FLOOR OR GROUND AREA WITHIN THE REQUIRED
 CLEARANCES SHALL BE CLEAR & LEVEL. IN SWING DOORS
 REQUIRES 18??? CLEAR.
  
 7) A-2 RECEIVING ROOM OR BREAK ROOM PLEASE PROVIDE
 DETAILS ON SINK: 11-4.24.2 HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER OR RIM NO HIGHER THAN 34"
 ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 8) A-2 FRONT COUNTER PLEASE SHOW COMPLIANCE WITH:
 11-7.2 SALES AND SERVICE COUNTERS, TELLER WINDOWS,
 INFORMATION COUNTERS.
 (1) IN DEPARTMENT STORES AND MISCELLANEOUS RETAIL
 STORES WHERE COUNTERS HAVE CASH REGISTERS AND ARE
 PROVIDED FOR SALES OR DISTRIBUTION OF GOODS OR SERVICES
 TO THE PUBLIC, AT LEAST ONE OF EACH TYPE SHALL HAVE A
 PORTION OF THE COUNTER WHICH IS AT LEAST 36 INCHES (915
 MM) IN LENGTH WITH A MAXIMUM HEIGHT OF 36 INCHES (915
 MM) ABOVE THE FINISH FLOOR. IT SHALL BE ON AN
 ACCESSIBLE ROUTE COMPLYING WITH SECTION 11-4.3. THE
 ACCESSIBLE COUNTERS MUST BE DISPERSED THROUGHOUT THE
 BUILDING OR FACILITY. IN ALTERATIONS WHERE IT IS
 TECHNICALLY INFEASIBLE TO PROVIDE AN ACCESSIBLE
 COUNTER, AN AUXILIARY COUNTER MEETING THESE
 REQUIREMENTS MAY BE PROVIDED.
  
 (2) AT TICKETING COUNTERS, TELLER STATIONS IN A BANK,
 REGISTRATION COUNTERS IN HOTELS AND MOTELS, BOX OFFICE
 TICKET COUNTERS, AND OTHER COUNTERS THAT MAY NOT HAVE A
 CASH REGISTER BUT AT WHICH GOODS OR SERVICES ARE SOLD
 OR DISTRIBUTED, EITHER:
  
 (I) A PORTION OF THE MAIN COUNTER WHICH IS A MINIMUM OF
 36 INCHES (915 MM) IN LENGTH SHALL BE PROVIDED WITH A
 MAXIMUM HEIGHT OF 36 INCHES (915 MM); OR
  
 (II) AN AUXILIARY COUNTER WITH A MAXIMUM HEIGHT OF 36
 IN (915 MM) IN CLOSE PROXIMITY TO THE MAIN COUNTER
 SHALL BE PROVIDED; OR
  
 (III) EQUIVALENT FACILITATION SHALL BE PROVIDED (E.G.,
 AT A HOTEL REGISTRATION COUNTER, EQUIVALENT
 FACILITATION MIGHT CONSIST OF:
  
 (1) PROVISION OF A FOLDING SHELF ATTACHED TO THE MAIN
 COUNTER ON WHICH AN INDIVIDUAL WITH DISABILITIES CAN
 WRITE, AND
  
 (2) USE OF THE SPACE ON THE SIDE OF THE COUNTER OR AT
 THE CONCIERGE DESK, FOR HANDING MATERIALS BACK AND
 FORTH).
  
 ALL ACCESSIBLE SALES AND SERVICE COUNTERS SHALL BE ON
 AN ACCESSIBLE ROUTE COMPLYING WITH SECTION 11-4.3.
  
 9) 11-4.30.6SIGNAGE, ACCESSIBILITY, MOUNTING LOCATION
 AND HEIGHT. WHERE PERMANENT IDENTIFICATION IS PROVIDED
 FOR ROOMS AND SPACES, SIGNS SHALL BE INSTALLED ON THE
 WALL ADJACENT TO THE LATCH SIDE OF THE DOOR. WHERE
 THERE IS NO WALL SPACE TO THE LATCH SIDE OF THE DOOR,
 INCLUDING AT DOUBLE LEAF DOORS, SIGNS SHALL BE PLACED
 ON THE NEAREST ADJACENT WALL. MOUNTING HEIGHT SHALL BE
 60 INCHES (1525 MM) ABOVE THE FINISH FLOOR TO THE
 CENTERLINE OF THE SIGN. MOUNTING LOCATION FOR SUCH
 SIGNAGE SHALL BE SO THAT A PERSON MAY APPROACH WITHIN 3
 INCHES (76 MM) OF SIGNAGE WITHOUT ENCOUNTERING
 PROTRUDING OBJECTS OR STANDING WITHIN THE SWING OF A
 DOOR.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved