2010-12-17 14:15:551000--45TH STREET, BUILDING #1
 PERMIT #10120405
 REVIEW COMMENTS - FIRE
  
  
 PROVIDE SIGNAGE AT THE FIRE DEPARTMENT CONNECTIONS
 IDENTIFYING WHICH CONNECTIONS SUPPLY WHICH BUILDING.
  
 PROVIDE A LOCAL WATERFLOW ALARM. THIS ALARM SHALL ALSO
 BE TIED INTO THE BUILDING FIRE ALARM SYSTEM PER SECTION
 6.6.8.1 OF NFPA 13R.
  
 PROVIDE SPRINKLER PROTECTION IN THE SPRINKLER RISER
 ROOM.
  
 PAGE 5 OF THE HYDRAULIC CALCULATIONS IS MISSING. PAGE 5
 SHOWS THE CONNECTION OF THE NODES, FRICTION LOSS, ETC.
  
 NOTE: THE SPRINKLER SYSTEM HAS BEEN DESIGNED TO NFPA
 13R. THE SPRINKLER SYSTEM HYDRAULICS HAVE BEEN
 CONSERVATIVELY DESIGNED TO NFPA 13 STANDARDS USING A
 DESIGN DENSITY OF 0.10 GPM/SQ.FT. IN LIEU OF THE
 SPECIFIC LISTED FLOW REQUIREMENTS (BASED UPON MAXIMUM
 SPRINKLER COVERAGE) OF NFPA 13R. THE SPECIFIC FLOW FOR
 16 FT. X 16 FT. SPRINKLER COVERAGE IS SHOWN AS 13 GPM
 IN THE PRODUCT DATA. A DESIGN DENSITY OF 0.10
 GPM/SQ.FT. FOR 16 FT. X 16 FT. RESULTS IN A COVERAGE
 AREA OF 256 SQ.FT. EQUATING TO 25.6 GPM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730
  