2010-12-20 13:23:57 | 1000--45TH STREET, BUILDING NO. 3 | | PERMIT #10120404 | | REVIEW COMMENTS - FIRE | | | | | | THE FOLLOWING ROOMS ARE CONSIDERED OUTSIDE THE DWELLING | | UNIT AND SHOULD BE PROTECTED WITH STANDARD SPRAY | | SPRINKLERS PER NFPA 13: | | DINING (3-114) | | STORAGE (3-120A/B) | | CLEAN LAUNDRY (3-122) | | | | A LOCAL WATERFLOW SHALL BE PROVIDED AND THE ALARM SHALL | | BE CONNECTED TO THE BUILDING FIRE ALARM SYSTEM PER | | SECTION 6.6.8 OF NFPA 13R. | | | | SPRINKLER PROTECTION OMMITED FROM EXTERIOR CLOSET | | (3-130). VERIFY NO UNPROTECTED PENETRATIONS ENTER THE | | DWELLING UNIT PER SECTION 6.8.6 OF NFPA 13R. | | | | SEVERAL BRANCH LINES SUPPLY MORE THAN TWO | | RESIDENTIAL-TYPE SPRINKLERS; THIS IS NOT SUPPORTED BY | | THE HYDRAULIC CALCULATIONS. | | | | PROVIDE SIGNAGE FOR FIRE DEPARTMENT CONNECTION LABELING | | WHICH BUILDING IS SUPPLIED BY THE CONNECTION. | | | | SCOPE OF WORK SHOWS AN INSTALLATION OF 144 SPRINKLERS. | | THE JOB VALUE LISTED ON THE PERMIT APPLICATION APPEARS | | TO BE UNDER-VALUED AT $6,500. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW |
|